Skip to main content
Schneider Electric CR1F500FZ7 — Contactors

Schneider CR1F500FZ7 TeSys F Magnetic Latching Contactor, 50

MPNCR1F500FZ7
Obsolete

Schneider Electric TeSys F magnetic latching contactor, CR1F500FZ7, 3P, 500 A rated operational current, 110 V DC low-consumption coil, 335 kW at 690 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

CR1F500FZ7 — Identification
ParameterValue
Product / component typeMagnetic latching contactor
Series / rangeTeSys
ApplicationMotor control Resistive load
CR1F500FZ7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)1000 V AC 25...200 Hz
Utilisation categoryAC-1 AC-3 AC-4
CR1F500FZ7 — Contacts & Poles
ParameterValue
Pole configuration3P
CR1F500FZ7 — Environmental
ParameterValue
Operating altitude3000 m without derating
Protective treatment / pollution degreeTH
CR1F500FZ7 — Mechanical
ParameterValue
Width233 mm
Height238 mm
Depth232 mm

Product details

The CR1F500FZ7 is a TeSys F magnetic latching contactor from Schneider Electric — 3-pole, rated for 500 A operational current (AC-3 duty) and a 110 V DC low-consumption latching coil. It's built for motor control and resistive loads across AC-1, AC-3, and AC-4 utilization categories. The latching mechanism holds the main contacts closed with a 550 W DC pulse and unlatches at 60 W DC, meaning the coil only draws power during the switching event — no continuous hold-in power, which matters for applications where coil heating or energy efficiency is a concern.

The motor power table backs that up: 335 kW at 690 V, 280 kW at 415 V, 250 kW at 380–400 V. For UL/CSA installations, the horsepower ratings are 500 hp at 575–600 V and 400 hp at 460–480 V. The 110 V DC low-consumption coil has a latching voltage tolerance of 0.85–1.1 Uc, so it picks up reliably down to about 93.5 V DC and drops out at the same threshold. The unlatching coil draws 60 W DC — a separate pulse to release the latch. This dual-coil latching design is common in applications where a momentary power loss must not drop the load (e.g., conveyor hold, crane brakes).

This is a frame-style contactor — 232 mm deep, 233 mm wide, 238 mm high — sized for bolted busbar connections. The terminals accept lugs or ring terminals on up to 2 cables of 240 mm² each, or busbars up to 40 x 5 mm. Tightening torque is 35 N·m, so a torque wrench is expected during installation. The TH protective treatment (tropicalization) means it's coated for humid or mildly corrosive environments, but it's not rated for washdown — no IP rating is listed, so it belongs in a ventilated enclosure, not on the open floor.

The contactor carries a rated insulation voltage (Ui) of 1000 V conforming to IEC 60158-1, IEC 60947-4, and BS 775, plus 1500 V conforming to VDE 0110 group C. These are the core electrical safety certifications for industrial control gear — they confirm the part meets IEC/EN 60947-4-1 for contactors and motor starters. No UL/CSA listing number is explicitly stated in the spec record, but the horsepower ratings for UL/CSA imply UL recognition or CSA certification for the North American market. RoHS and REACH compliance is standard for Schneider's TeSys range, though not explicitly cited in this ledger.

Frequently asked questions

What is the closest alternative to CR1F500FZ7 in the TeSys F family?

Within the TeSys F range, the CR1F500FZ7 is a magnetic latching contactor with a 110 V DC coil. The closest sibling would be a standard electrically held contactor of the same frame size and current rating (e.g., LC1F500) if latching is not required. The physical footprint and lug connections are shared across the F-frame, so a swap between latching and non-latching variants is mechanically compatible but requires a control-circuit rewire.

What is the depth of CR1F500FZ7?

The depth is 232 mm.

What range does CR1F500FZ7 belong to?

It belongs to the TeSys range, specifically the TeSys F series of contactors.

What compliance documentation does Schneider provide for CR1F500FZ7?

The contactor is certified to IEC 60158-1, IEC 60947-4, BS 775, and VDE 0110 group C for insulation voltage, with an 8 kV rated impulse withstand voltage. UL/CSA horsepower ratings are listed, indicating North American market acceptance. RoHS and REACH declarations are standard for Schneider's TeSys range, though not explicitly cited in this spec record.

MPN
CR1F500FZ7