Skip to main content
Schneider Electric CR1F6304Q7 — Contactors

Schneider TeSys F CR1F6304Q7 Magnetic Latching Contactor, 63

MPNCR1F6304Q7
Active

Schneider Electric TeSys F CR1F6304Q7 magnetic latching contactor, 4-pole NO, 630 A rated operational current, 380 V AC 50/60 Hz coil, 1000 V AC rated insulation voltage.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

CR1F6304Q7 — Identification
ParameterValue
Product / component typeMagnetic latching contactor
Series / rangeTeSys
ApplicationResistive load Motor control
CR1F6304Q7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)1000 V AC 25...200 Hz
Utilisation categoryAC-1 AC-3 AC-4
CR1F6304Q7 — Contacts & Poles
ParameterValue
Pole configuration4P
CR1F6304Q7 — Environmental
ParameterValue
IP degree of protectionIP20 front face IEC 60529
Operating altitude9842.52 ft (3000 m) without derating
Protective treatment / pollution degreeTH
CR1F6304Q7 — Approvals
ParameterValue
StandardsNF C 63-110 VDE 0660 BS 5424 JEM 1038 IEC 60947-4
CR1F6304Q7 — Mechanical
ParameterValue
Width15.3 in (389 mm)
Height12.0 in (304 mm)
Depth10.04 in (255 mm)

Product details

The Schneider Electric TeSys F CR1F6304Q7 is a magnetic latching contactor — it stays in its last commanded position without continuous coil power, which means no holding current and less heat in the panel. It's a 4-pole normally-open device rated for 630 A operational current at up to 1000 V AC, covering utilisation categories AC-1 (resistive), AC-3 (squirrel-cage motor starting), and AC-4 (plugging/inching). Motor power ratings span 200 kW at 220–230 V up to 450 kW at 690–1000 V AC, 50/60 Hz. For UL/CSA installations, it's rated 250 hp at 200–208 V through 800 hp at 575–600 V, three-phase.

Control and coil considerations

The control circuit is 380 V AC 50/60 Hz, with both latching and unlatching operating limits of 0.85–1.1 Uc. Latching draws 2300 VA (AC or DC); unlatching draws only 11 VA. Operating time is 40–80 ms to latch, 50–100 ms to unlatch.

Mounts on a notched AM1-EC rail. Dimensions: 15.3 inches wide, 12.0 inches high, 10.04 inches deep — plan your enclosure depth accordingly. Power connections use bars sized 60 x 5 mm, torqued to 513.3 lbf·in (58 N·m). Associated fuse rating is 630 A aM or gG at ≤ 440 V for the power circuit.

Breaking capacity and durability

Rated breaking capacity reaches 6300 A at 220–440 V, 5400 A at 500 V, 4600 A at 660/690 V, and 3200 A at 1000 V for the power circuit. Making capacity is 6740 A rms.

Compliant with IEC 60947-4, NF C 63-110, VDE 0660, BS 5424, and JEM 1038. Rated insulation voltage is 1000 V per IEC 60947-4 and BS 775, with a VDE 0110 group C rating of 1500 V. Altitude rating is 3000 m without derating. Protective treatment is TH (tropicalized).

Frequently asked questions

What is CR1F6304Q7's depth for panel layout?

The depth is 10.04 inches (255 mm). Combined with a width of 15.3 inches and height of 12.0 inches, this is a large-frame contactor requiring generous enclosure depth.

What motor power can CR1F6304Q7 handle?

Motor power ratings vary by voltage: 200 kW at 220–230 V, 335 kW at 380–400 V, 375 kW at 415 V, 400 kW at 440 V and 500–660 V, and 450 kW at 690 V and 1000 V AC, 50/60 Hz. UL/CSA ratings range from 250 hp at 200–208 V to 800 hp at 575–600 V.

What compliance standards does CR1F6304Q7 meet?

It complies with IEC 60947-4, NF C 63-110, VDE 0660, BS 5424, and JEM 1038. Rated insulation voltage is 1000 V per IEC 60947-4 and BS 775, with a VDE 0110 group C rating of 1500 V.

MPN
CR1F6304Q7