MCCB for distribution panels — 32 A, 60 kA at 240 V
It delivers 60 kA Icu at 220/240 V AC and 30 kA at 380/400 V AC, both per IEC 60947-2. That breaking capacity means it clears high-fault currents on a distribution board without upstream fuses needing to blow — useful for a main or subfeed breaker in a 400 V panel where SCCR requirements are tight.
Fixed backplate mount, 75 mm wide, 130 mm tall, 60 mm deep. The 25 mm pole pitch matches standard busbar spacing. Neutral position is left.
Protection and duty ratings
Thermal-magnetic trip with fixed long-time delay at 1 In and a magnetic instantaneous pickup of 300 kA integral. Category A (no intentional short-time delay), so it trips instantly on fault — coordination with downstream breakers relies on current selectivity, not time grading. Electrical endurance is 4000 cycles at 415 V at half rated current per IEC 60947-2; mechanical endurance is 13000 cycles. Suitable for isolation, with 690 V rated insulation voltage and pollution degree 3.