Skip to main content
Schneider Electric EZS100F3050 — Circuit Breaker Accessories

Schneider Electric EZS100F3050 EasyPact EZS, 50 A, 3-Pole, 6

MPNEZS100F3050
Obsolete

Schneider Electric EasyPact EZS, circuit breaker, EZS100F3050, 3P, 50 A, TM-D trip unit, 60 kA Icu at 240 V AC, fixed backplate mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

EZS100F3050 — Identification
ParameterValue
Product / component typeCircuit breaker
Range of productEasyPact EZS
EZS100F3050 — Electrical
ParameterValue
Network type (AC/DC)AC
Rated current [In]50 A at 40 °C
Rated operational voltage [Ue]440 V AC 50/60 Hz conforming to EN/IEC 60947-2 400 V AC 50/60 Hz conforming to GB 14048.2
Rated insulation voltage [Ui]690 V conforming to EN/IEC 60947-2
Rated impulse withstand voltage [Uimp]6 kV conforming to EN/IEC 60947-2
Network frequency50/60 Hz
Poles description3P
EZS100F3050 — Protection & Performance
ParameterValue
Breaking capacity60 kA Icu at 220/240 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 380/400 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 415 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 65 kA Icu at 200/230 V AC 50/60 Hz conforming to GB 14048.2 35 kA Icu at 380/400 V AC 50/60 Hz conforming to GB 14048.2
Rated service breaking capacity [Ics]30 kA at 220/230 V AC 50/60 Hz conforming to GB 14048.2 17 kA at 380/400 V AC 50/60 Hz conforming to GB 14048.2 30 kA at 220/240 V AC 50/60 Hz conforming to EN/IEC 60947-2 17 kA at 380/400 V AC 50/60 Hz conforming to EN/IEC 60947-2
Breaking capacity codeF
Trip unit technologyThermal-magnetic
Trip unit rating50 A at 40 °C
Trip unit nameTM-D
Protection typeOverload protection (thermal) Short-circuit protection (magnetic)
Suitability for isolationYes
Utilisation categoryCategory A
Mechanical durability13000 cycles conforming to EN/IEC 60947-2 20000 cycles conforming to GB 14048.2
Electrical durability4000 cycles 415 V In/2 conforming to EN/IEC 60947-2 8000 cycles 400 V In conforming to GB 14048.2
EZS100F3050 — Mechanical
ParameterValue
Connection pitch25 mm
Downside connectionFront
Upside connectionFront
Device short nameEZS100F
Control typeToggle
Mounting modeFixed
Mounting supportBackplate
Width75 mm
Height130 mm
Depth60 mm
EZS100F3050 — Environmental
ParameterValue
IP degree of protectionIP40 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Pollution degree3 conforming to IEC 60947-1
Operating ambient air temperature-35...70 °C
Storage ambient air temperature-50...85 °C
EZS100F3050 — Approvals
ParameterValue
StandardsIEC 60947-2 EN 60947-2

Product details

What this breaker does for a panel

It's built for distribution duty in an AC network — think branch-circuit protection in a panel feeding motor control centers or lighting sub-distribution. The fixed backplate mount and front-front connections keep wiring predictable; the toggle handle is right there for manual switching.

The F breaking-capacity code means 60 kA Icu at 240 V AC, 30 kA at 400 V, and 20 kA at 440 V — all per IEC 60947-2. That's enough to sit downstream of a larger main breaker without worrying about cascading failure. The integral instant protection is rated 500 kA, so the magnetic trip responds fast on a bolted fault. Category A utilization (no intentional short-time delay) means it's a standard distribution breaker, not a selective main. Pair it with a properly sized upstream device for full selectivity.

Fixed backplate mount, 25 mm connection pitch. Neutral position is left, so plan your busbar layout accordingly.

Frequently asked questions

Where can I buy the EZS100F3050?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.

What is the breaking capacity of the EZS100F3050?

60 kA Icu at 240 V AC, 30 kA at 400 V, and 20 kA at 440 V, all per IEC 60947-2.

MPN