Schneider Electric G12E4A50 — Miniature Circuit Breakers (MCB)

Schneider GoPact G12E4A50 MCCB 4P 50A TM-D, 15 kA

MPNG12E4A50
Active

Schneider Electric GoPact MCCB 125 series, G12E4A50, 4-pole moulded case circuit breaker, 50 A rated current, TM-D thermal-magnetic trip unit, 15 kA breaking capacity at 415 V AC, screw terminals, front connections, Grey (RAL 7035).

$106.22Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

G12E4A50 — Identification
ParameterValue
Product nameGoPact MCCB 125
Product range (series)GoPact MCCB
Product/component typeCircuit breaker
Device applicationDistribution
G12E4A50 — Ratings
ParameterValue
Rated current (In)50 A at 40 °C
Poles configuration4P
Rated operational voltage (Ue)415 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated insulation voltage (Ui)440 V AC conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Utilisation categoryCategory A
Overvoltage categoryIII
G12E4A50 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)8000 cycles at 415 V In
Mechanical durability (cycles)30000 cycles
G12E4A50 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
G12E4A50 — Environmental
ParameterValue
Operating ambient temperature-20...55 °C
Storage ambient temperature-35...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
G12E4A50 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H
G12E4A50 — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity15 kA Icu at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Ics] rated service short-circuit breaking capacity15 kA at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2
G12E4A50 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.8...1 x In
Trip unit protection functionsLI

Product details

What you're looking at

Schneider GoPact G12E4A50 — a 4-pole moulded case circuit breaker (MCCB) from the GoPact MCCB 125 family, rated 50 A at 40 °C with a TM-D thermal-magnetic trip unit. The LI protection curve handles overload (thermal) and short-circuit (magnetic) faults.

Fixed-mount, backplate installation. Screw terminals front-top and front-bottom, 25 mm connection pitch. Neutral on the left, 4D protected poles (neutral fully rated at 1 x Ir). Overvoltage category III.

No official direct successor listed; the GoPact MCCB 125 family remains active.

Utilisation category A (non-delayed, no intentional short-time delay) — use it downstream of a current-limiting fuse or upstream breaker for selective coordination per IEC 60947-2 Annex H. Electrical endurance 8000 cycles at rated current; mechanical 30000 cycles.

Operating altitude 0–2000 m without derating, 2000–5000 m with derating.

Frequently asked questions

Where can I buy G12E4A50?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.

What is G12E4A50's breaking capacity?

15 kA at 380/415 V AC, utilisation category A, per EN/IEC 60947-2.

What trip unit does G12E4A50 use?

TM-D thermal-magnetic trip unit with LI protection: thermal overload (L) and magnetic short-circuit (I).

Is G12E4A50 suitable for isolation?

Yes, it is certified suitable for isolation per EN/IEC 60947-2. The toggle position gives positive indication of contact state.

MPN