Skip to main content
Schneider Electric G12E4F50 — Miniature Circuit Breakers (MCB)

Schneider Electric G12E4F50 GoPact MCCB 4P 50A TM-D, 15 kA

MPNG12E4F50
Active

Schneider Electric GoPact MCCB 125, 4P, 50 A at 40 °C, TM-D thermal-magnetic trip, 15 kA at 380/415 V AC, screw terminals, IP20, grey RAL 7035.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

G12E4F50 — Identification
ParameterValue
Product nameGoPact MCCB 125
Product range (series)GoPact MCCB
Product/component typeCircuit breaker
Device applicationDistribution
G12E4F50 — Ratings
ParameterValue
Rated current (In)50 A at 40 °C
Poles configuration4P
Rated operational voltage (Ue)415 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated insulation voltage (Ui)440 V AC conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Utilisation categoryCategory A
Overvoltage categoryIII
G12E4F50 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)8000 cycles at 415 V In
Mechanical durability (cycles)30000 cycles
G12E4F50 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
G12E4F50 — Environmental
ParameterValue
Operating ambient temperature-20...55 °C
Storage ambient temperature-35...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
G12E4F50 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H
G12E4F50 — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity15 kA Icu at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Ics] rated service short-circuit breaking capacity15 kA at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2
G12E4F50 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range1 x In
Trip unit protection functionsLI

Product details

Fit and mounting — what to check before you swap

The G12E4F50: Fixed mount on a backplate (not DIN rail). 100 mm wide, 130 mm tall, 60 mm deep — that's a compact footprint for a 4-pole 50 A MCCB. Screw terminals up top and down below, both front-accessed, so you can land cables without reaching around the back. Connection pitch is 25 mm, standard for this class. Neutral is on the left when viewed from the front. IP20 finger-safe terminals, fine for enclosed panels; not for washdown.

The TM-D trip unit gives you LI protection: thermal overload (L) and magnetic short-circuit (I). The thermal element tracks heating in the conductor, so you can size it for a feeder or a moderate motor load — but this is a distribution breaker (Category A), not a motor-protective device with adjustable overload curves. The magnetic trip is fixed, not adjustable. 8000 electrical cycles at 415 V at full rated current; 30000 mechanical cycles. That's service life for a panel feeder that sees a few operations a year, not a switching-duty contactor.

Frequently asked questions

What is G12E4F50 used for?

It's a 4-pole molded-case circuit breaker rated 50 A at 40 °C with a TM-D thermal-magnetic trip, used for overload and short-circuit protection in distribution panels and feeder circuits in light industrial and commercial installations.

What compliance documentation does this brand provide for G12E4F50?

The G12E4F50 is designed to EN/IEC 60947-1, EN/IEC 60947-2, and EN/IEC 60947-2 Annex H. It carries IP20 protection per IEC 60529 and is rated for isolation per EN/IEC 60947-2.

Where can I buy G12E4F50 and how is it quoted?

We source the G12E4F50 through independent distribution and quote it to order against an RFQ. Availability and current pricing are confirmed at quote time.

MPN
G12E4F50