Skip to main content
Schneider Electric GS1QQBR4 — Contactors

GS1QQBR4 TeSys GS Fuse Switch Disconnector Body, 400 A, Obso

MPNGS1QQBR4
Obsolete

Schneider Electric TeSys GS GS1QQBR4 fuse switch disconnector body, 4 poles, BS fuse type, 400 A rated, obsolete.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

GS1QQBR4 — Identification
ParameterValue
Product / component typeFuse switch disconnector body
GS1QQBR4 — Contacts & Poles
ParameterValue
Pole configuration4P
GS1QQBR4 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529 (with terminal cover)
Protective treatment / pollution degreeTH
Fire resistance960 °C body conforming to IEC 60695-2-1 850 °C fuse cover conforming to IEC 60695-2-1
GS1QQBR4 — Approvals
ParameterValue
StandardsIEC 60269-2 IEC 60269-1 IEC 60947-3
GS1QQBR4 — Mechanical
ParameterValue
Width337 mm
Height205 mm
Depth149 mm

Product details

The GS1QQBR4 is a fuse switch disconnector body from the Schneider Electric TeSys GS range, designed for 4-pole (4P) isolation and protection of AC and DC circuits using BS-type fuses. Rated at 400 A conventional free-air thermal current (Ith) at 40 °C, it handles motor and resistive loads across multiple duty classes: 400 A at 400 V AC-23B, 315 A at 500 V AC-23B, and 250 A at 690 V AC-23B, with corresponding power ratings up to 400 kW at 500 V AC-23A. Breaking capacity is 3200 A at 400 V AC-23B, with a making capacity of 4000 A at the same voltage — sufficient for isolating motor circuits under load, but the 80 kA short-circuit withstand rating means it relies on upstream BS fuses for fault clearance.

Mounts on a plate or rail — the 337 mm width and 205 mm height mean it needs a generous panel cutout, and the 149 mm depth accounts for the fuse carrier and terminal bars. Power circuit connections accept bars or screw terminals for 185 to 240 mm² flexible cable; control circuit and power terminals both torque to 25 N·m.

The 400 A AC-23B rating is the motor-switching current at 400 V — that's the figure that governs real motor isolation duty, not the higher 400 A Ith which is a free-air thermal rating for continuous resistive load. Rated impulse withstand voltage of 8 kV and insulation voltage of 800 V AC. Electrical durability is 1000 cycles for AC-23A/B and 200 cycles for DC-23A/B — this is a switch-disconnector, not a contactor for frequent cycling; mechanical durability is 10,000 cycles. Fire resistance tested to 960 °C on the body and 850 °C on the fuse cover per IEC 60695-2-1, with TH protective treatment for tropical environments.

Designed and tested to IEC 60269-1, IEC 60269-2 (fuse standards), and IEC 60947-3 (switch-disconnector standard).

Frequently asked questions

What are the key ratings for GS1QQBR4?

Rated 400 A Ith at 40 °C, 400 A at 400 V AC-23B motor duty, breaking capacity 3200 A at 400 V AC-23B, making capacity 4000 A at 400 V AC-23B, and 80 kA short-circuit withstand with upstream BS fuses.

What is the physical size of GS1QQBR4?

Width 337 mm, height 205 mm, depth 149 mm.

What standards does GS1QQBR4 comply with?

IEC 60269-1, IEC 60269-2, and IEC 60947-3.

How do I source this obsolete part?

Submit an RFQ with the full order code and quantity. We source through surplus and broker channels — no firm stock or lead time can be stated without a request.

MPN
GS1QQBR4