The TeSys Deca GV2DM202P7 is a reversing motor starter combination — a pre-assembled block that integrates a 3-pole reversing contactor with a GV2ME motor circuit breaker in one DIN-rail mountable package. Thermal protection is adjustable from 0.16 to 0.25 A. The magnetic trip is fixed at 2.4 A. Rated breaking capacity is 50 kA at 400/415 V and 440 V per IEC 60947-4-1. That is the fault current the combination can safely interrupt — useful for high-available-fault panels where a lower-rated starter would need upstream fusing or a current-limiting breaker.
The GV2DM202P7 measures 90 mm wide, 176.4 mm high, and 99.6 mm deep.
Control circuit and motor power