The GV2DM203P7 is a reversing motor starter from the TeSys Deca range, combining a 3-pole reversing contactor, a GV2AF3 combination block, and a GV2ME motor circuit breaker in one assembly. It is rated for AC-3 utilisation category, so it is built for switching three-phase induction motors under full load — the standard duty for reversing starters on conveyors, pumps, and small drives. The thermal protection adjustment range of 0.25...0.4 A sets the overload relay to match the motor's full-load current; for a 0.09 kW motor at 400/415 V, that is the correct window. The control circuit runs on 230 V AC 50/60 Hz, and the unit delivers a rated breaking capacity of 50 kA at 400/415 V (IEC 60947-4-1) — meaning it can safely interrupt a fault current up to that level without damaging upstream gear, provided the installation meets Type 1 coordination (the starter may need replacement after a fault, but the feeder breaker stays intact).
The GV2DM203P7 measures 90 mm wide, 176.4 mm high, and 99.6 mm deep. It mounts directly to a DIN rail or panel plate via the TeSys Deca base plate.