Skip to main content
Schneider Electric GV2DM205BL — Miniature Circuit Breakers (MCB)

Schneider GV2DM205BL TeSys Reversing Motor Starter, 0.63-1 A

MPNGV2DM205BL
Active

Schneider Electric TeSys Deca reversing motor starter GV2DM205BL, thermal adjustment 0.63-1 A, 24 V DC coil, 3-pole, AC-3 utilisation category, 50 kA breaking capacity at 400 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

GV2DM205BL — Identification
ParameterValue
Product range (series)TeSys
Product/component typeMotor starter
GV2DM205BL — Ratings
ParameterValue
Poles configuration3P
Utilisation categoryAC-3
GV2DM205BL — Mechanical
ParameterValue
Width90 mm
Height176.4 mm
Depth99.6 mm
GV2DM205BL — Other specifications
ParameterValue
Motor power0.25 kW at 400/415 V AC 50/60 Hz 0.37 kW at 400/415 V AC 50/60 Hz 0.25 kW at 440 V AC 50/60 Hz 0.37 kW at 440 V AC 50/60 Hz
Coordination typeType 1
Device short nameGV2DM
Device composition1 combination block GV2AF3 1 motor circuit breaker type GV2ME 1 3-pole reversing contactor
Motor starter typeReversing
Breaking capacityIq 50 kA at 400/415 V conforming to IEC 60947-4-1 Iq 50 kA at 440 V conforming to IEC 60947-4-1 Iq 50 kA at 500 V conforming to IEC 60947-4-1
Magnetic tripping current13 A
Coil voltage24 V DC
Thermal protection adjustment range0.63...1 A

Product details

It combines a GV2ME motor circuit breaker, a GV2AF3 combination block, and a 3-pole reversing contactor in one DIN-rail-mounted unit. The thermal protection adjustment range is 0.63 to 1 A, sized for motors drawing 0.25 kW at 400/415 V AC or 0.37 kW at 440 V AC (50/60 Hz). The control circuit runs on 24 V DC.

Rated for AC-3 utilisation category — the standard for squirrel-cage motor switching — so the 0.63-1 A thermal range directly governs the motor full-load current you can protect. The magnetic trip is fixed at 13 A, providing short-circuit protection above the thermal band. Breaking capacity is 50 kA at 400/415 V and 440 V per IEC 60947-4-1, meaning it can safely interrupt a fault current up to that level without upstream fuses needing to clear first. Type 1 coordination means the starter remains operational after a short circuit but may need contact replacement — typical for panel designs where downtime for swap-out is acceptable.

Mounts on standard DIN rail. Dimensions are 90 mm wide, 176.4 mm high, 99.6 mm deep — the width is the critical fill factor on a crowded rail; the depth leaves clearance for wiring ducts and gland plates.

Frequently asked questions

What is the thermal adjustment range of GV2DM205BL?

The thermal protection adjustment range is 0.63 to 1 A, covering motor full-load currents in that band.

Where can I buy GV2DM205BL?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
GV2DM205BL