Skip to main content
Schneider Electric GV2ME01AP — Molded Case Circuit Breakers (MCCB)

Schneider TeSys GV2ME01AP Motor Circuit Breaker, 0.16 A, 100

MPNGV2ME01AP
Active

Schneider Electric TeSys Deca GV2ME01AP motor circuit breaker, 3-pole, 0.16 A rated current, thermal-magnetic trip, 100 kA breaking capacity, IP20, DIN-rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

GV2ME01AP — Identification
ParameterValue
Product / component typeMotor circuit breaker
Device applicationMotor protection
GV2ME01AP — Mechanical
ParameterValue
Height89 mm
Width45 mm
Depth78.5 mm
GV2ME01AP — Electrical
ParameterValue
[In] rated current0.16 A
Breaking capacity100 kA Icu at 230/240 V AC 50 Hz conforming to IEC 60947-2 100 kA Icu at 400/415 V AC 50 Hz conforming to IEC 60947-2 100 kA Icu at 440 V AC 50 Hz conforming to IEC 60947-2 100 kA Icu at 500 V AC 50 Hz conforming to IEC 60947-2 100 kA Icu at 690 V AC 50 Hz conforming to IEC 60947-2
[Ue] rated operational voltage690 V AC 50 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage690 V AC 50/60 Hz conforming to IEC 60947-2
GV2ME01AP — Specifications
ParameterValue
Poles description3P
Trip unit technologyThermal-magnetic
Device short nameGV2ME
StandardsEN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1

Product details

Its rated current is 0.16 A, with a thermal protection adjustment range of 0.1...0.16 A and a magnetic tripping current of 1.93 A. This means it's sized for the smallest fractional-horsepower motors — think tiny fans, pumps, or conveyor drives drawing under 0.2 A full-load.

The 45 mm width means it takes a single modular space on the rail. Accepts power wiring up to 6 mm² solid or 4 mm² flexible with ferrule, torqued to 1.7 N·m. Horizontal or vertical mounting position, no derating needed.

Listed to EN/IEC 60947-2 (circuit-breaker standard) and EN/IEC 60947-4-1 (motor-starter standard), plus UL 60947-4-1 and CSA C22.2 No 60947-4-1. That covers the major North American and international regulatory jurisdictions. Also carries a 960 °C glow-wire fire resistance rating per IEC 60695-2-11. Phase-failure sensitive per IEC 60947-4-1, and suitable for isolation per IEC 60947-1.

Frequently asked questions

What is GV2ME01AP's rated current and what size motor does it protect?

Rated current is 0.16 A, with a thermal adjustment range of 0.1...0.16 A. The magnetic trip is fixed at 1.93 A. This protects the smallest fractional-horsepower motors — typically under 0.05 kW at 400 V.

What breaking capacity does GV2ME01AP have?

100 kA Icu at 230/240 V, 400/415 V, 440 V, 500 V, and 690 V AC, 50 Hz, per IEC 60947-2. That's a high interrupting rating for a breaker this small — it can handle high fault current without cascading upstream.

What compliance documentation does this brand provide for GV2ME01AP?

The part carries UL 60947-4-1, CSA C22.2 No 60947-4-1, and EN/IEC 60947-2 and 60947-4-1 certifications. It also meets IEC 60695-2-11 glow-wire at 960 °C. RoHS and REACH compliance is standard for the TeSys range, though specific declarations are issued per shipment.

What is GV2ME01AP's listed depth?

78.5 mm depth, 89 mm height, 45 mm width. Fits a standard 35 mm DIN-rail footprint.

MPN
GV2ME01AP