Schneider Electric GV2ME04A — Molded Case Circuit Breakers (MCCB)

Schneider GV2ME04A TeSys Motor Circuit Breaker, 0.63 A

MPNGV2ME04A
Active

Schneider Electric TeSys Deca GV2ME04A, motor circuit breaker, 0.63 A, 3 poles, thermal-magnetic, 100 kA breaking capacity.

$109.65Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

GV2ME04A — Identification
ParameterValue
Product / component typeMotor circuit breaker
Device applicationMotor protection
GV2ME04A — Mechanical
ParameterValue
Height4.0 in (101 mm)
Width1.8 in (45 mm)
Depth3.09 in (78.5 mm)
GV2ME04A — Electrical
ParameterValue
Breaking capacity100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 100 kA Icu 440 V AC 50/60 Hz IEC 60947-2 100 kA Icu 500 V AC 50/60 Hz IEC 60947-2 100 kA Icu 690 V AC 50/60 Hz IEC 60947-2
[Ue] rated operational voltage690 V AC 50/60 Hz IEC 60947-2
[Ui] rated insulation voltage690 V AC 50/60 Hz IEC 60947-2
GV2ME04A — Specifications
ParameterValue
Poles description3P
Trip unit technologyThermal-magnetic
Device short nameGV2ME
StandardsEN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-2-40:Annex JJ IEC/EN 60335-1:Clause 30.2

Product details

GV2ME04A is a 3-pole motor circuit breaker from the TeSys Deca family, rated 0.63 A line current with a thermal-magnetic trip unit. It clips onto 35 mm DIN rail (45 mm wide, 78.5 mm deep) and is meant for motor protection in panels or machine control. The magnetic trip picks up at 9.3 A, and it’s phase-failure sensitive—so it covers both overload and single-phasing on three-phase motors. It's Category A per IEC 60947-2 and rated for motor switching per IEC 60947-4-1.

The 0.63 A is fixed—set at the factory for that line current. Magnetic trip at 9.3 A protects against shorts. Power dissipation is 2.5 W per pole, so the breaker runs cool even at full load. For high-density panels, that matters more than you’d think. Suitable for isolation (per IEC 60947-1), so it doubles as a disconnect if the panel’s safety scheme allows downstream work without a separate switch.

Sourcing reality

No direct plug-and-play replacement; the GV2ME family shares the same footprint across ratings (45 mm wide, same mounting), but each ampere rating is a fixed overcurrent setting. If the BOM says 0.63 A, stick with this code.

Frequently asked questions

What compliance documentation is available?

Listed standards include EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and IEC/EN 60335-2-40 annex JJ and 60335-1 clause 30.2.

What is the color and depth of the GV2ME04A?

Color is dark grey; depth is 3.09 in (78.5 mm).

Is there a pin-compatible alternative?

Mechanically identical to other TeSys Deca GV2ME breakers, but the 0.63 A rating is fixed. For a different current you'd order the corresponding GV2ME code, but this one is specific to 0.63 A.

MPN