Skip to main content
Schneider Electric GV2ME04AE11TQ — Molded Case Circuit Breakers (MCCB)

Schneider GV2ME04AE11TQ Motor Circuit Breaker, 0.63 A, 100 k

MPNGV2ME04AE11TQ
Active

Schneider Electric TeSys Deca GV2ME04AE11TQ motor circuit breaker, 3-pole, 0.63 A rated current, 100 kA breaking capacity, thermal-magnetic trip, IP20, DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

GV2ME04AE11TQ — Identification
ParameterValue
Product / component typeMotor circuit breaker
Device applicationMotor protection
GV2ME04AE11TQ — Mechanical
ParameterValue
Height89 mm
Width45 mm
Depth78.5 mm
GV2ME04AE11TQ — Electrical
ParameterValue
[In] rated current0.63 A
Breaking capacity100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage600 V AC 50/60 Hz conforming to UL 508 690 V AC 50/60 Hz conforming to IEC 60947-2 600 V AC 50/60 Hz conforming to CSA C22.2 No 14
[Ui] rated insulation voltage690 V AC 50/60 Hz conforming to IEC 60947-2
GV2ME04AE11TQ — Specifications
ParameterValue
Poles description3P
Trip unit technologyThermal-magnetic
Device short nameGV2ME
StandardsEN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-2-40:Annex JJ IEC/EN 60335-1:Clause 30.2

Product details

The Schneider GV2ME04AE11TQ is a TeSys Deca motor circuit breaker — a 3-pole thermal-magnetic device rated at 0.63 A continuous current, designed to protect motor circuits against overload and short-circuit faults. It's part of the GV2ME family, built for motor protection duty in control panels and motor starter assemblies. The 0.63 A rating matches small motors — think fractional-horsepower pumps, fans, or conveyor drives — and the thermal-magnetic trip gives you both inverse-time overload protection and instantaneous magnetic short-circuit protection.

This breaker carries a 100 kA Icu breaking capacity across the board — at 230/240 V, 400/415 V, 440 V, 500 V, and 690 V AC. That's a high-fault rating for a 0.63 A device, meaning it can sit upstream of a small motor without worrying about cascading failure under a dead-short. It's certified to EN/IEC 60947-2 and 60947-4-1, plus UL 60947-4-1 and CSA C22.2 No 60947-4-1 — so it's accepted in European, North American, and Canadian panels. The utilisation category is AC-3 and AC-3e per IEC 60947-4-1, which is standard for squirrel-cage motor switching — starting, stopping, and running motors under load. Category A per IEC 60947-2 means it's not intended for selective coordination, so it's a straightforward motor-protector, not a line-side main breaker.

The power terminals are screw-clamp, accepting up to 2 cables of 1–6 mm² solid or 1.5–6 mm² flexible without ferrules.

Frequently asked questions

What is the breaking capacity of this breaker?

100 kA Icu at 230/240 V, 400/415 V, 440 V, 500 V, and 690 V AC, per IEC 60947-2.

What motor power does this breaker support?

It's rated for 0.12 kW at 400/415 V AC, 0.18 kW at 400/415 V AC, and 0.37 kW at 690 V AC, all at 50/60 Hz.

Does it have phase-failure protection?

Yes, phase-failure sensitivity is built in per IEC 60947-4-1.

What certifications does it carry?

It complies with EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, IEC/EN 60335-2-40 Annex JJ, and IEC/EN 60335-1 Clause 30.2.

MPN
GV2ME04AE11TQ