Skip to main content
Schneider Electric GV2ME05A — Molded Case Circuit Breakers (MCCB)

Schneider GV2ME05A Motor Circuit Breaker, 1A, 100kA

MPNGV2ME05A
Active

Schneider Electric TeSys GV2 motor circuit breaker, GV2ME05A, 1 A line rated, 100 kA breaking capacity, 3-pole thermal-magnetic.

$109.65Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

GV2ME05A — Identification
ParameterValue
Product / component typeMotor circuit breaker
Device applicationMotor protection
GV2ME05A — Mechanical
ParameterValue
Height4.0 in (101 mm)
Width1.8 in (45 mm)
Depth3.09 in (78.5 mm)
GV2ME05A — Electrical
ParameterValue
Breaking capacity100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 100 kA Icu 440 V AC 50/60 Hz IEC 60947-2 100 kA Icu 500 V AC 50/60 Hz IEC 60947-2 100 kA Icu 690 V AC 50/60 Hz IEC 60947-2
[Ue] rated operational voltage690 V AC 50/60 Hz IEC 60947-2
[Ui] rated insulation voltage690 V AC 50/60 Hz IEC 60947-2
GV2ME05A — Specifications
ParameterValue
Poles description3P
Trip unit technologyThermal-magnetic
Device short nameGV2ME
StandardsEN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-2-40:Annex JJ IEC/EN 60335-1:Clause 30.2

Product details

TeSys GV2 motor circuit breaker

The Schneider Electric GV2ME05A is a TeSys GV2 motor circuit breaker rated at 1 A line current with a 100 kA breaking capacity across 230–690 V AC, making it one of the highest interrupting ratings for a device this size. Thermal-magnetic trip unit, magnetic trip point at 15.1 A. Rated for motor protection under IEC/EN 60947-4-1 and UL 60947-4-1, it also serves as a disconnecting means (isolation suitable per IEC 60947-1).

Mounting & dimensions

Dimensions: 45 mm wide (1.8 in), 78.5 mm deep, 101 mm high. IP20 on front face, IK04 impact resistance. Power terminals accept 0.5–2.5 mm² solid or 0.5–4 mm² flexible without cable end.

Frequently asked questions

What is the color of the GV2ME05A?

Dark grey.

What is the depth of the GV2ME05A?

3.09 in (78.5 mm).

What compliance standards does the GV2ME05A meet?

It complies with EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and IEC/EN 60335-2-40 Annex JJ, among others.

MPN
GV2ME05A