Schneider Electric GV2ME05K1B7 — Miniature Circuit Breakers (MCB)

Schneider GV2ME05K1B7 TeSys DOL Starter, 0.63-1A, 24V AC

MPNGV2ME05K1B7
Obsolete

Schneider Electric TeSys GV2-ME DOL combination motor starter, GV2ME05K1B7, 0.63...1 A thermal protection, 24 V AC 50/60 Hz coil, 3-pole, non-reversing.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

GV2ME05K1B7 — Identification
ParameterValue
Product rangeTeSys
Product/component typeMotor starter
GV2ME05K1B7 — Ratings
ParameterValue
Poles configuration3P
Breaking capacity50 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1
Utilisation categoryAC-3
GV2ME05K1B7 — Mechanical
ParameterValue
Width45 mm
Height152 mm
Depth87 mm
GV2ME05K1B7 — Other specifications
ParameterValue
Motor power0.25 kW at 400/415 V AC 50/60 Hz 0.37 kW at 400/415 V AC 50/60 Hz 0.25 kW at 440 V AC 50/60 Hz 0.37 kW at 440 V AC 50/60 Hz
Coordination typeType 1
Device short nameGV2ME
Device composition1 motor circuit breaker type GV2ME 1 3-pole contactor 1 combination block GV2AF01
Motor starter typeNon reversing
Magnetic tripping current13 A
Coil voltage24 V AC 50/60 Hz
Thermal protection adjustment range0.63...1 A

Product details

The Schneider GV2ME05K1B7 is a TeSys GV2-ME DOL (direct-on-line) combination motor starter, integrating a GV2ME motor circuit breaker, a 3-pole contactor, and a GV2AF01 combination block into a single unit. It provides coordinated motor starting, overload protection, and short-circuit protection for a 3-phase motor. The thermal protection adjustment range is 0.63...1 A, making it suited for small motors in that full-load current band. The magnetic tripping current is fixed at 13 A, providing instantaneous short-circuit protection above that threshold. Rated for utilisation category AC-3 (squirrel-cage motor starting/switching), it delivers a breaking capacity of 50 kA Iq at 400/415 V AC conforming to IEC 60947-4-1 — sufficient for high-fault-capacity industrial panels without requiring upstream current-limiting fuses in many configurations.

This footprint matches the standard TeSys GV2ME family, so an existing panel layout for a GV2ME starter can accept this unit without re-drilling or re-spacing. The coordination type is Type 1, meaning the starter may require replacement of the contactor after a short-circuit fault — factor that into spares planning for critical machinery.

Motor power coverage

At 400/415 V AC 50/60 Hz, the GV2ME05K1B7 covers motor ratings of 0.25 kW and 0.37 kW. This dual-power listing means the same starter handles both standard European 400 V and 440 V supply systems without re-rating.

Frequently asked questions

What is the thermal protection range of the GV2ME05K1B7?

The thermal protection adjustment range is 0.63...1 A, set via the dial on the front of the motor circuit breaker section.

What breaking capacity does this starter provide?

It provides 50 kA Iq at both 400/415 V AC and 440 V AC, conforming to IEC 60947-4-1. This is the rated short-circuit breaking capacity of the combination unit.

What control voltage does the coil require?

The control circuit voltage is 24 V AC at 50/60 Hz.

What are the physical dimensions of the GV2ME05K1B7?

Width is 45 mm, height is 152 mm, and depth is 87 mm. It mounts on a standard DIN rail.

MPN