Skip to main content
Schneider Electric GV2ME05K1P7 — Miniature Circuit Breakers (MCB)

Schneider GV2ME05K1P7 TeSys DOL Starter, 0.63-1 A, 230 V AC

MPNGV2ME05K1P7
Obsolete

Schneider Electric TeSys GV2-ME DOL combination starter, GV2ME05K1P7, 0.63...1 A thermal protection, 230 V AC control, 3-pole, non-reversing.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

GV2ME05K1P7 — Identification
ParameterValue
Product rangeTeSys
Product/component typeMotor starter
GV2ME05K1P7 — Ratings
ParameterValue
Poles configuration3P
Breaking capacity50 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1
Utilisation categoryAC-3
GV2ME05K1P7 — Mechanical
ParameterValue
Width45 mm
Height152 mm
Depth87 mm
GV2ME05K1P7 — Other specifications
ParameterValue
Motor power0.25 kW at 400/415 V AC 50/60 Hz 0.37 kW at 400/415 V AC 50/60 Hz 0.25 kW at 440 V AC 50/60 Hz 0.37 kW at 440 V AC 50/60 Hz
Coordination typeType 1
Device short nameGV2ME
Device composition1 motor circuit breaker type GV2ME 1 combination block GV2AF01 1 3-pole contactor
Motor starter typeNon reversing
Magnetic tripping current13 A
Coil voltage230 V AC 50/60 Hz
Thermal protection adjustment range0.63...1 A

Product details

The Schneider GV2ME05K1P7 is a TeSys GV2-ME direct-on-line (DOL) combination motor starter, integrating a motor circuit breaker, a combination block (GV2AF01), and a 3-pole contactor in one unit. It's a non-reversing starter sized for small motor loads, with a thermal protection adjustment range of 0.63 to 1 A. Rated for AC-3 utilisation category, it delivers motor power ratings of 0.25 kW and 0.37 kW at 400/415 V AC and 440 V AC, 50/60 Hz. Its breaking capacity is 50 kA Iq at both 400/415 V and 440 V AC, conforming to IEC 60947-4-1, with Type 1 coordination.

The 0.63...1 A thermal protection range is the critical selection parameter — it sets the overload trip point for the motor. A motor with a full-load current (FLA) between 0.63 and 1 A is the correct match; outside that band, the starter won't protect properly. The magnetic tripping current is fixed at 13 A, handling short-circuit protection.

The starter is a 3-pole unit with dimensions of 152 mm height, 45 mm width, and 87 mm depth. The combination block (GV2AF01) is pre-assembled, reducing wiring time — just connect the motor leads to the breaker output and the control voltage to the contactor coil.

Frequently asked questions

What are the key ratings I need to check for fit?

The thermal protection adjustment range is 0.63...1 A — match this to your motor's full-load current. The control circuit voltage is 230 V AC. The breaking capacity is 50 kA at 400/415 V AC, ensuring it handles high fault currents.

How do I source this obsolete part?

Submit an RFQ. We hold last-time-buy stock and can quote availability. Once our stock is depleted, the part will only be available through the surplus channel.

MPN
GV2ME05K1P7