Schneider Electric GV2ME06AE11TQ — Molded Case Circuit Breakers (MCCB)

Schneider GV2ME06AE11TQ Motor Circuit Breaker, 1.6 A, 100 kA

MPNGV2ME06AE11TQ
Obsolete

Schneider Electric TeSys GV2 motor circuit breaker, GV2ME06AE11TQ, 1.6 A rated current, 100 kA breaking capacity, thermal-magnetic trip, 3-pole, IP20, DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

GV2ME06AE11TQ — Identification
ParameterValue
Product / component typeMotor circuit breaker
Device applicationMotor protection
GV2ME06AE11TQ — Mechanical
ParameterValue
Height89 mm
Width45 mm
Depth78.5 mm
GV2ME06AE11TQ — Electrical
ParameterValue
[In] rated current1.6 A
Breaking capacity100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Ics at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Ics at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Ics at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Ics at 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage600 V AC 50/60 Hz conforming to UL 508 690 V AC 50/60 Hz conforming to IEC 60947-2 600 V AC 50/60 Hz conforming to CSA C22.2 No 14
[Ui] rated insulation voltage690 V AC 50/60 Hz conforming to IEC 60947-2
GV2ME06AE11TQ — Specifications
ParameterValue
Poles description3P
Trip unit technologyThermal-magnetic
Device short nameGV2ME
StandardsEN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-2-40:Annex JJ IEC/EN 60335-1:Clause 30.2

Product details

Breaking capacity is 100 kA at 230/240 V, 400/415 V, 440 V, 500 V, and 690 V AC — both Icu (ultimate) and Ics (service) ratings are 100 kA across that range.

Dimensions are 89 mm high, 45 mm wide, 78.5 mm deep — a compact 3-pole footprint that fits standard motor-control-center buckets. Screw-clamp terminals accept up to 2 cables of 1–6 mm² solid or 1.5–6 mm² flexible without cable end, or 1–4 mm² flexible with cable end. Tightening torque is 1.7 N·m. The IP20 finger-safe enclosure suits open mounting in a cabinet; the IK04 impact rating handles incidental tool contact during panel assembly. Rated for horizontal or vertical mounting. Fire resistance tested at 960 °C per IEC 60695-2-11. These ratings confirm the breaker is suitable for standard industrial environments without derating for altitude or ambient temperature within the normal range.

Compliant with EN/IEC 60947-2 (circuit-breaker standard), EN/IEC 60947-4-1 (contactor/motor-starter standard), UL 60947-4-1, and CSA C22.2 No 60947-4-1. Also meets IEC/EN 60335-2-40 Annex JJ and IEC/EN 60335-1 Clause 30.2 for household-appliance motor circuits. The UL/CSA marks mean it is accepted in North American panels without additional agency review. Phase failure sensitivity per IEC 60947-4-1 is built in — the breaker trips on loss of one phase, protecting the motor from single-phasing.

Sourcing and BOM fit

Rated for AC-3 and AC-3e utilization categories per IEC 60947-4-1 — the standard motor-switching duty. Electrical durability is 100,000 cycles at 415 V under AC-3 and AC-3e loads. Mechanical durability is also 100,000 cycles. These endurance figures match the typical life of a small motor starter in a packaging line or conveyor system. The auxiliary contact composition is 1 NO + 1 NC front-mounted, providing feedback for PLC inputs or status indication without an add-on block. Power dissipation per pole is 2.5 W, totaling 7.5 W for the three poles at rated current. This heat must be considered in enclosure thermal calculations, especially in sealed cabinets. The part is supplied as a set of 20 units, which aligns with OEM build quantities and reduces per-unit packaging waste.

Frequently asked questions

What are the key ratings for the GV2ME06AE11TQ?

Rated current is 1.6 A with a thermal-magnetic trip unit. Breaking capacity is 100 kA at 230/240 V, 400/415 V, 440 V, 500 V, and 690 V AC. Magnetic tripping current is 26.2 A. It is a 3-pole motor circuit breaker with phase failure sensitivity.

What compliance documentation does this part carry?

It is certified to EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and IEC/EN 60335 series standards. The UL and CSA marks cover North American installations.

What is the mounting and connection detail?

Mounts on 35 mm DIN rail or panel with adaptor plate. Screw-clamp terminals accept 1–6 mm² solid or 1.5–6 mm² flexible wire. Dimensions are 89 x 45 x 78.5 mm (H x W x D).

MPN