Skip to main content
Schneider Electric GV2ME06AN11TQ — Miniature Circuit Breakers (MCB)

Schneider GV2ME06AN11TQ Motor Circuit Breaker, 1.6 A, 100 kA

MPNGV2ME06AN11TQ
Obsolete

Schneider Electric TeSys GV2 motor circuit breaker, GV2ME06AN11TQ, 1.6 A rated current, 100 kA breaking capacity, thermal-magnetic trip, 3-pole.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

GV2ME06AN11TQ — Identification
ParameterValue
Product nameTeSys GV2
Product rangeTeSys Deca
Product/component typeMotor circuit breaker
Device applicationMotor protection
GV2ME06AN11TQ — Ratings
ParameterValue
Rated current (In)1.6 A
Poles configuration3P
Breaking capacity100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)600 V AC 50/60 Hz conforming to UL 508 690 V AC 50/60 Hz conforming to IEC 60947-2 600 V AC 50/60 Hz conforming to CSA C22.2 No 14
Rated insulation voltage (Ui)690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz conforming to IEC 60947-2
Utilisation categoryCategory A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1 AC-3e conforming to IEC 60947-4-1
GV2ME06AN11TQ — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Suitability for isolationYes conforming to IEC 60947-1
Electrical durability (cycles)100000 cycles for AC-3 at 415 V In 100000 cycles for AC-3e at 415 V In
Mechanical durability (cycles)100000 cycles
GV2ME06AN11TQ — Mechanical
ParameterValue
Control typePush-button
Terminal connection typePower circuit: screw clamp terminal 2 cable(s) 1...6 mm²solid Power circuit: screw clamp terminal 2 cable(s) 1.5...6 mm²flexible without cable end Power circuit: screw clamp terminal 2 cable(s) 1...4 mm²flexible with cable end
Terminal tightening torque1.7 N.m - on screw clamp terminal
Width54 mm
Height89 mm
Depth78.5 mm
GV2ME06AN11TQ — Environmental
ParameterValue
Operating ambient temperature-20...40 °C in enclosure -20...60 °C open mounted
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to IEC 60529 (open mounted)
GV2ME06AN11TQ — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-2-40:Annex JJ IEC/EN 60335-1:Clause 30.2
GV2ME06AN11TQ — Electrical
ParameterValue
[Ics] rated service short-circuit breaking capacity100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2

Product details

Part identity and compliance envelope

The Schneider Electric GV2ME06AN11TQ is a TeSys GV2 motor circuit breaker, a 3-pole thermal-magnetic device rated at 1.6 A continuous current. It is designed for motor protection (category AC-3 and AC-3e per IEC 60947-4-1) and circuit protection (category A per IEC 60947-2). The breaking capacity is 100 kA Icu across the full voltage range from 230/240 V to 690 V AC, certified to IEC 60947-2. Standards compliance is fully documented: EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, plus IEC/EN 60335-2-40 Annex JJ and IEC/EN 60335-1 Clause 30.2 for fire resistance. The part carries a 960 °C glow-wire rating per IEC 60695-2-11.

Installation and integration constraints

Mounting options: clips onto 35 mm symmetrical DIN rail, or screws to a panel using an adaptor plate. Both horizontal and vertical orientations are permitted. Dimensions are 89 mm height, 54 mm width, 78.5 mm depth — fits standard motor-starter footprints. Power connections accept screw-clamp terminals: 2 x 1–6 mm² solid, or 2 x 1.5–6 mm² flexible without ferrule, or 2 x 1–4 mm² flexible with ferrule. Tightening torque is 1.7 N·m. Built-in auxiliary contacts: 1 NO + 1 NC side-mounted. IP20 protection when open-mounted (finger-safe), IK04 impact resistance. Climatic withstand conforms to IACS. Operating altitude is limited to 2000 m.

Electrical performance and trip characteristics

Thermal-magnetic trip: the magnetic (short-circuit) trip threshold is 26.2 A, which is approximately 16.4 x In. This provides rapid clearing of high faults while riding through motor inrush. Power dissipation per pole is 2.5 W, so total heat at rated load is 7.5 W — factor into enclosure thermal calculations. Electrical durability: 100,000 cycles at AC-3 / AC-3e at 415 V at rated current. Mechanical durability matches at 100,000 cycles. The device is rated for uninterrupted duty per IEC 60947-4-1. Motor power ratings span 0.37 kW to 1.1 kW depending on line voltage (400/415 V, 500 V, 690 V AC). The 1.6 A frame covers small motors, fans, and pumps in the fractional-to-1.1 kW range.

Frequently asked questions

What are the key standards this part is certified to?

It is certified to EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, plus IEC/EN 60335-2-40 Annex JJ and IEC/EN 60335-1 Clause 30.2 for fire resistance.

What is the breaking capacity of the GV2ME06AN11TQ?

100 kA Icu at all rated voltages from 230/240 V through 690 V AC, conforming to IEC 60947-2.

Does this motor circuit breaker include phase-failure protection?

Yes, phase-failure sensitivity is built in, conforming to IEC 60947-4-1.

What auxiliary contacts are included on the GV2ME06AN11TQ?

It comes with 1 NO + 1 NC side-mounted auxiliary contacts.

MPN