Schneider Electric GV2ME06K1BW3 — Molded Case Circuit Breakers (MCCB)

Schneider GV2ME06K1BW3 TeSys DOL Starter, 1-1.6A, 24VDC

MPNGV2ME06K1BW3
Obsolete

Schneider Electric TeSys GV2-ME DOL combination starter, GV2ME06K1BW3, 1...1.6 A thermal protection, 24 V DC coil, 3-pole non-reversing.

$155.03Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

GV2ME06K1BW3 — Identification
ParameterValue
Product / component typeMotor starter
GV2ME06K1BW3 — Mechanical
ParameterValue
Height152 mm
Width45 mm
Depth87 mm
GV2ME06K1BW3 — Electrical
ParameterValue
Breaking capacity50 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1
GV2ME06K1BW3 — Specifications
ParameterValue
Poles description3P
Device short nameGV2ME
GV2ME06K1BW3 — Other specifications
ParameterValue
RangeTeSys
Motor power0.37 kW at 400/415 V AC 50/60 Hz 0.55 kW at 400/415 V AC 50/60 Hz 0.37 kW at 440 V AC 50/60 Hz 0.55 kW at 440 V AC 50/60 Hz 0.37 kW at 500 V AC 50/60 Hz 0.55 kW at 500 V AC 50/60 Hz 0.75 kW at 500 V AC 50/60 Hz
Coordination typeType 1
Device composition1 3-pole contactor 1 motor circuit breaker type GV2ME 1 combination block GV2AF01
Motor starter typeNon reversing
Utilisation categoryAC-3 AC-3e
Magnetic tripping current22.5 A
Coil voltage24 V DC
Thermal protection adjustment range1...1.6 A

Product details

The GV2ME06K1BW3 is a non-reversing DOL combination starter from the TeSys GV2-ME range, integrating a 3-pole contactor, a GV2ME motor circuit breaker, and a GV2AF01 combination block into a single assembly. Its thermal protection adjustment range of 1 to 1.6 A and 24 V DC control circuit make it a direct fit for small motor applications in that amp window.

The 1...1.6 A thermal adjustment range sets the motor FLC this starter protects — set the dial to the motor's nameplate full-load current. The magnetic trip is fixed at 22.5 A, clearing short-circuit faults without nuisance tripping on normal starting inrush.

Schneider has marked the GV2ME06K1BW3 as obsolete.

It is a 3-pole device rated for AC-3 and AC-3e utilization categories, meaning it is built for starting and stopping squirrel-cage induction motors under load. Coordination is Type 1, so after a fault the starter may need component replacement rather than being immediately reusable.

Frequently asked questions

What motor power does this starter cover?

It covers 0.37 kW to 0.75 kW depending on supply voltage — 0.37 kW at 400/415 V, 0.55 kW at 440 V, and 0.37/0.55/0.75 kW across the 500 V range, all at 50/60 Hz.

What is the control voltage and coil type?

The control circuit is 24 V DC. This is the coil voltage for the integrated contactor.