It integrates a 3-pole contactor, a GV2ME motor circuit breaker, and a GV2AF01 combination block into a single unit, saving panel space and wiring time compared to assembling those components separately. Rated for AC-3 utilization category, it's built for starting and stopping squirrel-cage induction motors under load. The thermal protection adjustment range of 1...1.6 A sets the overload trip point, so you match it to the motor's full-load current. The magnetic trip is fixed at 22.5 A, providing short-circuit protection coordinated with the thermal overload.
Motor power coverage
The GV2ME06K1FE7 covers motor power ratings from 0.37 kW up to 0.75 kW depending on the supply voltage. At 400/415 V it handles 0.37 kW or 0.55 kW; at 500 V it covers 0.37 kW, 0.55 kW, and 0.75 kW. That voltage-dependent power range is typical for IEC motor starters — the same thermal overload element works across a range of line voltages.
As a TeSys GV2-ME family member, it shares the same footprint and combination block interface as other ratings in the series. If your motor FLA changes, swapping to a different GV2ME thermal adjustment range is straightforward without re-paneling.
Physical integration
Dimensions are 152 mm height, 45 mm width, and 87 mm depth.