Skip to main content
Schneider Electric GV2ME06K1M7 — Miniature Circuit Breakers (MCB)

Schneider Electric GV2ME06K1M7 TeSys DOL Starter, 1-1.6 A, 2

MPNGV2ME06K1M7
Obsolete

Schneider Electric TeSys GV2-ME DOL combination starter, GV2ME06K1M7, 1...1.6 A thermal protection, 220...230 V AC coil, 50 kA breaking capacity.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

GV2ME06K1M7 — Identification
ParameterValue
Product rangeTeSys
Product/component typeMotor starter
GV2ME06K1M7 — Ratings
ParameterValue
Poles configuration3P
Breaking capacity50 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1
Utilisation categoryAC-3
GV2ME06K1M7 — Mechanical
ParameterValue
Width45 mm
Height152 mm
Depth87 mm
GV2ME06K1M7 — Other specifications
ParameterValue
Motor power0.37 kW at 400/415 V AC 50/60 Hz 0.55 kW at 400/415 V AC 50/60 Hz 0.37 kW at 440 V AC 50/60 Hz 0.55 kW at 440 V AC 50/60 Hz 0.37 kW at 500 V AC 50/60 Hz 0.55 kW at 500 V AC 50/60 Hz 0.75 kW at 500 V AC 50/60 Hz
Coordination typeType 1
Device short nameGV2ME
Device composition1 combination block GV2AF01 1 3-pole contactor 1 motor circuit breaker type GV2ME
Motor starter typeNon reversing
Magnetic tripping current22.5 A
Coil voltage220/230 V AC 50/60 Hz
Thermal protection adjustment range1...1.6 A

Product details

The GV2ME06K1M7 is a non-reversing DOL combination starter from the TeSys GV2-ME series, integrating a 3-pole motor circuit breaker and a contactor in a single block. Thermal protection adjusts from 1 to 1.6 A, and the control circuit is rated for 220/230 V AC 50/60 Hz. The magnetic tripping current is set at 22.5 A.

Rated breaking capacity is 50 kA Iq at 400/415 V, 440 V, and 500 V AC, conforming to IEC 60947-4-1. Coordination type is Type 1, meaning the starter is not guaranteed to remain functional after a fault — the breaker clears the short circuit, but the contactor may need replacement. This is standard for applications where fault isolation speed is prioritized over component survival.

Motor power and utilisation category

Rated for AC-3 utilisation (squirrel-cage motor starting and switching off during running). Motor power ratings span 0.37 kW to 0.75 kW depending on supply voltage: 0.37 kW at 400/415 V, 0.55 kW at 440 V, and up to 0.75 kW at 500 V. The 1-1.6 A thermal adjustment range covers the lower end of small motor protection.

The device composition includes one combination block GV2AF01, one 3-pole contactor, and one motor circuit breaker type GV2ME. Dimensions: 45 mm wide, 152 mm high, 87 mm deep — fits a standard DIN-rail enclosure footprint. The 45 mm width occupies a single modular space, leaving room for auxiliary blocks or a separate control transformer on the same rail.

Frequently asked questions

What is the thermal protection adjustment range?

The thermal protection adjustment range is 1 to 1.6 A, set via the dial on the front of the motor circuit breaker section.

What is the breaking capacity?

Breaking capacity is 50 kA Iq at 400/415 V, 440 V, and 500 V AC, conforming to IEC 60947-4-1.

What control voltage does this starter use?

The control circuit voltage is 220/230 V AC 50/60 Hz.

MPN