Skip to main content
Schneider Electric GV2ME06K1P7 — Molded Case Circuit Breakers (MCCB)

Schneider Electric GV2ME06K1P7 TeSys DOL Starter, 1-1.6 A, 2

MPNGV2ME06K1P7
Obsolete

Schneider Electric TeSys GV2-ME series, GV2ME06K1P7, DOL combination motor starter, 1...1.6 A thermal protection adjustment range, 230 V AC control voltage.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

GV2ME06K1P7 — Identification
ParameterValue
Product / component typeMotor starter
GV2ME06K1P7 — Mechanical
ParameterValue
Height152 mm
Width45 mm
Depth87 mm
GV2ME06K1P7 — Electrical
ParameterValue
Breaking capacity50 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1
GV2ME06K1P7 — Specifications
ParameterValue
Poles description3P
Device short nameGV2ME
GV2ME06K1P7 — Other specifications
ParameterValue
RangeTeSys
Motor power0.37 kW at 400/415 V AC 50/60 Hz 0.55 kW at 400/415 V AC 50/60 Hz 0.37 kW at 440 V AC 50/60 Hz 0.55 kW at 440 V AC 50/60 Hz 0.37 kW at 500 V AC 50/60 Hz 0.55 kW at 500 V AC 50/60 Hz 0.75 kW at 500 V AC 50/60 Hz
Coordination typeType 1
Device composition1 combination block GV2AF01 1 motor circuit breaker type GV2ME 1 3-pole contactor
Motor starter typeNon reversing
Utilisation categoryAC-3
Magnetic tripping current22.5 A
Coil voltage230 V AC 50/60 Hz
Thermal protection adjustment range1...1.6 A

Product details

The GV2ME06K1P7 is a non-reversing DOL combination starter from the TeSys GV2-ME line, integrating a motor circuit breaker and a 3-pole contactor in one block with the GV2AF01 auxiliary contact block. The thermal protection adjustment range of 1...1.6 A is the primary selection parameter — it sets the motor full-load current window the overload relay protects against. For a 0.37 kW motor at 400/415 V AC, that window lands correctly; the same block also covers 0.55 kW at 440 V and 0.75 kW at 500 V, per the motor power table. Rated AC-3 (AC-3) utilization category, so it is designed for starting squirrel-cage induction motors — switching under load during start, not for resistive heating banks. The magnetic tripping current is set at 22.5 A, which clears short-circuit faults fast without waiting for the thermal bimetal to respond. Breaking capacity is 50 kA Iq at 400/415 V AC conforming to IEC 60947-4-1, meaning the combination starter can safely interrupt a fault current up to 50 kA at those voltages without welding contacts or rupturing the enclosure. That is a high-fault rating for this frame size — suitable for installations with substantial transformer capacity or stiff utility feeds. Coordination type is Type 1, per IEC 60947-4-1. Under a short-circuit, the contactor may need replacement after the fault, but the starter remains serviceable. For applications requiring no-contact replacement after a fault, Type 2 coordination would be specified instead.

Mounts on a DIN rail. The 45 mm width (45 mm) and 152 mm height (152 mm) fit a standard modular enclosure grid; depth of 87 mm (87 mm) means it clears most shallow backboxes, but check gland-plate clearance if the panel is less than 100 mm deep. The control circuit voltage is 230 V AC 50/60 Hz (230 V AC 50/60 Hz) — the coil pulls in at that nominal; verify the control transformer secondary matches before wiring. The device composition includes the GV2AF01 auxiliary contact block as a factory-integrated element. No separate auxiliary purchase needed for basic interlocking.

Product status is Active (Active). This is a current-production catalog item, not a phase-out or last-time-buy. The TeSys GV2-ME series is a mature, widely stocked line — no PCN risk in the near term.

Frequently asked questions

What is the thermal protection adjustment range and what motor does it cover?

The thermal protection adjustment range is 1...1.6 A. At 400/415 V AC, that covers a 0.37 kW motor; at 440 V it covers 0.55 kW; at 500 V it covers 0.55 kW or 0.75 kW depending on the exact line voltage.

What breaking capacity does it have at 400 V?

50 kA Iq at 400/415 V AC, conforming to IEC 60947-4-1. That is the rated short-circuit making and breaking capacity for the combination starter.

What control voltage does the coil require?

230 V AC at 50/60 Hz. The coil is designed for that nominal voltage; verify the control transformer secondary matches before energizing.

MPN
GV2ME06K1P7