Schneider Electric GV2ME06K1Q7 — Molded Case Circuit Breakers (MCCB)

Schneider Electric GV2ME06K1Q7 TeSys DOL Starter, 1...1.6 A,

MPNGV2ME06K1Q7
Obsolete

Schneider Electric TeSys GV2-ME DOL combination starter, GV2ME06K1Q7, 1...1.6 A thermal adjustment, 380...400 V AC control, 50 kA breaking capacity.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

GV2ME06K1Q7 — Identification
ParameterValue
Product / component typeMotor starter
GV2ME06K1Q7 — Mechanical
ParameterValue
Height152 mm
Width45 mm
Depth87 mm
GV2ME06K1Q7 — Electrical
ParameterValue
Breaking capacity50 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1
GV2ME06K1Q7 — Specifications
ParameterValue
Poles description3P
Device short nameGV2ME
GV2ME06K1Q7 — Other specifications
ParameterValue
RangeTeSys
Motor power0.37 kW at 400/415 V AC 50/60 Hz 0.55 kW at 400/415 V AC 50/60 Hz 0.37 kW at 440 V AC 50/60 Hz 0.55 kW at 440 V AC 50/60 Hz 0.37 kW at 500 V AC 50/60 Hz 0.55 kW at 500 V AC 50/60 Hz 0.75 kW at 500 V AC 50/60 Hz
Coordination typeType 1
Device composition1 combination block GV2AF01 1 motor circuit breaker type GV2ME 1 3-pole contactor
Motor starter typeNon reversing
Utilisation categoryAC-3
Magnetic tripping current22.5 A
Coil voltage380/400 V AC 50/60 Hz
Thermal protection adjustment range1...1.6 A

Product details

It is a non-reversing starter rated for AC-3 duty (motor switching). The thermal protection adjustment range is 1...1.6 A, and the magnetic trip is fixed at 22.5 A.

Breaking capacity and motor power

Breaking capacity is 50 kA Iq at 400/415 V, 440 V, and 500 V AC 50/60 Hz, conforming to IEC 60947-4-1. Coordination type is Type 1. Motor power ratings span 0.37 kW to 0.75 kW depending on supply voltage — for example, 0.37 kW at 400/415 V and 0.55 kW at 440 V, with the 500 V rating reaching 0.75 kW.

The combination starter measures 152 mm high, 45 mm wide, and 87 mm deep. The depth of 87 mm is the dimension from the DIN rail to the front of the device — check enclosure depth clearance before committing.

Frequently asked questions

What is the thermal protection adjustment range?

The thermal overload adjustment range is 1...1.6 A. The magnetic trip is fixed at 22.5 A.

What breaking capacity does this starter provide?

It provides 50 kA Iq at 400/415 V, 440 V, and 500 V AC 50/60 Hz, conforming to IEC 60947-4-1.

What is the physical size of the GV2ME06K1Q7?

Height 152 mm, width 45 mm, depth 87 mm. The 45 mm width fits one standard DIN-rail slot.

MPN