The GV2ME06K1V7 is a non-reversing DOL combination starter from the TeSys GV2-ME series. It integrates a motor circuit breaker (type GV2ME) and a 3-pole contactor into a single 3P block, with a separate GV2AF01 combination block completing the assembly. The thermal protection adjustment range covers 1…1.6 A, and the magnetic tripping current is set at 22.5 A. Rated for AC-3 utilisation category, it delivers motor power ratings of 0.37 kW and 0.55 kW at 400/415 V AC 50/60 Hz, with the same dual ratings at 440 V and 500 V. At 500 V it also supports a 0.75 kW motor. The breaking capacity is 50 kA Iq at 400/415 V, 440 V, and 500 V AC, conforming to IEC 60947-4-1, with Type 1 coordination.
Schneider Electric GV2ME06K1V7 TeSys DOL Starter, 1…1.6 A, O
MPNGV2ME06K1V7
Obsolete
Schneider Electric TeSys GV2-ME DOL combination starter, GV2ME06K1V7, 1…1.6 A thermal protection, 400 V AC control, obsolete.
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
Specifications
| Parameter | Value |
|---|---|
| Product range | TeSys |
| Product/component type | Motor starter |
| Parameter | Value |
|---|---|
| Poles configuration | 3P |
| Breaking capacity | 50 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1 |
| Utilisation category | AC-3 |
| Parameter | Value |
|---|---|
| Width | 45 mm |
| Height | 152 mm |
| Depth | 87 mm |
| Parameter | Value |
|---|---|
| Motor power | 0.37 kW at 400/415 V AC 50/60 Hz 0.55 kW at 400/415 V AC 50/60 Hz 0.37 kW at 440 V AC 50/60 Hz 0.55 kW at 440 V AC 50/60 Hz 0.37 kW at 500 V AC 50/60 Hz 0.55 kW at 500 V AC 50/60 Hz 0.75 kW at 500 V AC 50/60 Hz |
| Coordination type | Type 1 |
| Device short name | GV2ME |
| Device composition | 1 combination block GV2AF01 1 motor circuit breaker type GV2ME 1 3-pole contactor |
| Motor starter type | Non reversing |
| Magnetic tripping current | 22.5 A |
| Coil voltage | 400 V AC 50/60 Hz |
| Thermal protection adjustment range | 1...1.6 A |
Product details
Frequently asked questions
What are the key ratings for GV2ME06K1V7?
Thermal protection adjustment 1…1.6 A, magnetic tripping current 22.5 A, AC-3 utilisation category, motor power 0.37/0.55 kW at 400/415 V, breaking capacity 50 kA at 400/415 V conforming to IEC 60947-4-1, Type 1 coordination.
MPN
GV2ME06K1V7