Skip to main content
Schneider Electric GV2ME06K2F7 — Miniature Circuit Breakers (MCB)

Schneider Electric GV2ME06K2F7 TeSys Reversing Motor Starter

MPNGV2ME06K2F7
Obsolete

Schneider Electric TeSys GV2-ME reversing DOL combination starter, GV2ME06K2F7, thermal protection 1...1.6 A, 110 V AC 50/60 Hz control.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

GV2ME06K2F7 — Identification
ParameterValue
Product rangeTeSys
Product/component typeMotor starter
GV2ME06K2F7 — Ratings
ParameterValue
Poles configuration3P
Breaking capacity50 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1
Utilisation categoryAC-3
GV2ME06K2F7 — Mechanical
ParameterValue
Width45 mm
Height152 mm
Depth87 mm
GV2ME06K2F7 — Other specifications
ParameterValue
Motor power0.37 kW at 400/415 V AC 50/60 Hz 0.55 kW at 400/415 V AC 50/60 Hz 0.37 kW at 440 V AC 50/60 Hz 0.55 kW at 440 V AC 50/60 Hz 0.37 kW at 500 V AC 50/60 Hz 0.55 kW at 500 V AC 50/60 Hz 0.75 kW at 500 V AC 50/60 Hz
Coordination typeType 1
Device short nameGV2ME
Device composition1 motor circuit breaker type GV2ME 1 3-pole reversing contactor 1 combination block GV2AF01
Motor starter typeReversing
Magnetic tripping current22.5 A
Coil voltage110 V AC 50/60 Hz
Thermal protection adjustment range1...1.6 A

Product details

The Schneider Electric GV2ME06K2F7 is a TeSys GV2-ME reversing DOL combination motor starter, built as a single assembly: one GV2ME motor circuit breaker, one 3-pole reversing contactor, and one GV2AF01 combination block. Thermal protection adjusts from 1 to 1.6 A, with a fixed magnetic trip at 22.5 A for short-circuit clearance. Breaking capacity is 50 kA Iq at 400/415 V, 440 V, and 500 V AC, conforming to IEC 60947-4-1, with Type 1 coordination — meaning the starter must be inspected and possibly replaced after a fault at that level.

Motor power and fit

Motor power ratings span 0.37 kW to 0.75 kW depending on supply voltage: 0.37 kW at 400/415 V and 440 V, 0.55 kW at 400/415 V and 440 V, and 0.37/0.55/0.75 kW at 500 V — all at 50/60 Hz. The 45 mm wide, 152 mm high, 87 mm deep footprint fits standard TeSys panel layouts and DIN-rail mounting.

This part is officially obsolete per the manufacturer.

Frequently asked questions

What is the thermal protection range of GV2ME06K2F7?

The thermal protection adjustment range is 1 to 1.6 A.

What is the control voltage for GV2ME06K2F7?

The control circuit voltage is 110 V AC 50/60 Hz.

What is the breaking capacity of GV2ME06K2F7?

Breaking capacity is 50 kA Iq at 400/415 V, 440 V, and 500 V AC, conforming to IEC 60947-4-1.

MPN
GV2ME06K2F7