Skip to main content
Schneider Electric GV2ME06K2M7 — Miniature Circuit Breakers (MCB)

Schneider GV2ME06K2M7 TeSys reversing starter, 1-1.6 A, obso

MPNGV2ME06K2M7
Obsolete

Schneider TeSys GV2-ME reversing combination starter, GV2ME06K2M7, 1...1.6 A thermal adjustment, 220/230 V AC control, 3-pole, AC-3, 50 kA breaking capacity.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

GV2ME06K2M7 — Identification
ParameterValue
Product rangeTeSys
Product/component typeMotor starter
GV2ME06K2M7 — Ratings
ParameterValue
Poles configuration3P
Breaking capacity50 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1
Utilisation categoryAC-3
GV2ME06K2M7 — Mechanical
ParameterValue
Width45 mm
Height152 mm
Depth87 mm
GV2ME06K2M7 — Other specifications
ParameterValue
Motor power0.37 kW at 400/415 V AC 50/60 Hz 0.55 kW at 400/415 V AC 50/60 Hz 0.37 kW at 440 V AC 50/60 Hz 0.55 kW at 440 V AC 50/60 Hz 0.37 kW at 500 V AC 50/60 Hz 0.55 kW at 500 V AC 50/60 Hz 0.75 kW at 500 V AC 50/60 Hz
Coordination typeType 1
Device short nameGV2ME
Device composition1 3-pole reversing contactor 1 combination block GV2AF01 1 motor circuit breaker type GV2ME
Motor starter typeReversing
Magnetic tripping current22.5 A
Coil voltage220/230 V AC 50/60 Hz
Thermal protection adjustment range1...1.6 A

Product details

The GV2ME06K2M7 is a DOL reversing combination starter from the TeSys GV2-ME series, integrating a 3-pole reversing contactor, a GV2AF01 combination block, and a motor circuit breaker into one unit. Its thermal protection adjusts from 1 to 1.6 A, and the control circuit runs on 220/230 V AC 50/60 Hz.

Rated for AC-3 utilisation category (switching squirrel-cage motors), the 50 kA breaking capacity at 400/415 V AC conforms to IEC 60947-4-1 — that means it can safely interrupt fault currents up to 50 kA without welding contacts or causing cascade failure upstream. The magnetic tripping current is set to 22.5 A, so short-circuit protection trips fast on a direct fault. Motor power ratings span 0.37 kW to 0.75 kW depending on line voltage (400 V through 500 V AC), so it covers small conveyor drives, pumps, and fan starters in that power band. The 45 mm width and 152 mm height fit standard DIN-rail enclosures — no special adaptor needed.

Schneider has marked this part obsolete. No official successor order code appears in the record, so the replacement path is not a straight cross-reference — you will need to evaluate a current TeSys GV2ME or GV3P variant for the same motor current range and control voltage.

Frequently asked questions

What replaces GV2ME06K2M7?

No official successor order code is listed. You will need to cross-reference a current TeSys GV2ME or GV3P starter with the same 1-1.6 A thermal adjustment range and 220/230 V AC control voltage.

What is the breaking capacity of this starter?

50 kA at 400/415 V AC, 440 V AC, and 500 V AC, conforming to IEC 60947-4-1. That is a Type 1 coordination rating — the starter protects the downstream motor but may need contact replacement after a fault.

What motor power range does it cover?

From 0.37 kW to 0.75 kW depending on line voltage (400 V to 500 V AC, 50/60 Hz). At 400/415 V it covers 0.37 kW and 0.55 kW; at 500 V it also covers 0.75 kW.

MPN