The GV2ME06K2M7 is a DOL reversing combination starter from the TeSys GV2-ME series, integrating a 3-pole reversing contactor, a GV2AF01 combination block, and a motor circuit breaker into one unit. Its thermal protection adjusts from 1 to 1.6 A, and the control circuit runs on 220/230 V AC 50/60 Hz.
Rated for AC-3 utilisation category (switching squirrel-cage motors), the 50 kA breaking capacity at 400/415 V AC conforms to IEC 60947-4-1 — that means it can safely interrupt fault currents up to 50 kA without welding contacts or causing cascade failure upstream. The magnetic tripping current is set to 22.5 A, so short-circuit protection trips fast on a direct fault. Motor power ratings span 0.37 kW to 0.75 kW depending on line voltage (400 V through 500 V AC), so it covers small conveyor drives, pumps, and fan starters in that power band. The 45 mm width and 152 mm height fit standard DIN-rail enclosures — no special adaptor needed.
Schneider has marked this part obsolete. No official successor order code appears in the record, so the replacement path is not a straight cross-reference — you will need to evaluate a current TeSys GV2ME or GV3P variant for the same motor current range and control voltage.