Skip to main content
Schneider Electric GV2ME06K2P7 — Miniature Circuit Breakers (MCB)

Schneider GV2ME06K2P7 TeSys Reversing Motor Starter, 1-1.6 A

MPNGV2ME06K2P7
Obsolete

Schneider Electric TeSys GV2-ME reversing combination starter, DOL, 1...1.6 A thermal protection, 230 V AC control, 3-pole, 50 kA breaking capacity.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

GV2ME06K2P7 — Identification
ParameterValue
Product rangeTeSys
Product/component typeMotor starter
GV2ME06K2P7 — Ratings
ParameterValue
Poles configuration3P
Breaking capacity50 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1
Utilisation categoryAC-3
GV2ME06K2P7 — Mechanical
ParameterValue
Width45 mm
Height152 mm
Depth87 mm
GV2ME06K2P7 — Other specifications
ParameterValue
Motor power0.37 kW at 400/415 V AC 50/60 Hz 0.55 kW at 400/415 V AC 50/60 Hz 0.37 kW at 440 V AC 50/60 Hz 0.55 kW at 440 V AC 50/60 Hz 0.37 kW at 500 V AC 50/60 Hz 0.55 kW at 500 V AC 50/60 Hz 0.75 kW at 500 V AC 50/60 Hz
Coordination typeType 1
Device short nameGV2ME
Device composition1 combination block GV2AF01 1 motor circuit breaker type GV2ME 1 3-pole reversing contactor
Motor starter typeReversing
Magnetic tripping current22.5 A
Coil voltage230 V AC 50/60 Hz
Thermal protection adjustment range1...1.6 A

Product details

The Schneider GV2ME06K2P7 is a reversing motor starter from the TeSys GV2-ME range — a pre-assembled combination block that pairs a GV2ME motor circuit breaker with a 3-pole reversing contactor and a GV2AF01 auxiliary contact block, all in one DIN-rail mountable package. It's rated for AC-3 duty (squirrel-cage motor switching) with a thermal protection adjustment range of 1 to 1.6 A, meaning it protects motors drawing that full-load current.

Breaking capacity is 50 kA at 400/415 V AC (per IEC 60947-4-1). The coordination type is Type 1, meaning after a fault the starter may need contactor replacement, but the breaker resets. Motor power ratings vary by voltage: 0.37 kW at 400/415 V, 0.55 kW at 440 V, and up to 0.75 kW at 500 V — pick the line voltage that matches your motor nameplate.

Integration notes

The reversing contactor pair is internally interlocked, so no external mechanical interlock is needed for direction change.

Frequently asked questions

What is the closest alternative to GV2ME06K2P7?

No official successor order code is listed. For a new design, check the current TeSys GV2-ME range for a starter with the same 1...1.6 A thermal adjustment and 50 kA breaking capacity at 400 V. The thermal trip range and fault rating are the critical fit parameters.

What is the depth of GV2ME06K2P7?

87 mm.

What range does GV2ME06K2P7 belong to?

TeSys.

What compliance documentation is available for GV2ME06K2P7?

The available records do not list specific compliance documentation (RoHS, REACH, UL, IEC) for this part. The breaking capacity is certified per IEC 60947-4-1.

MPN
GV2ME06K2P7