Schneider Electric GV2ME06K2Q7 — Miniature Circuit Breakers (MCB)

Schneider GV2ME06K2Q7 TeSys reversing starter, 1-1.6 A

MPNGV2ME06K2Q7
Active

Schneider Electric TeSys GV2-ME DOL reversing combination motor starter, GV2ME06K2Q7, thermal protection 1...1.6 A, 380...400 V AC control voltage.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

GV2ME06K2Q7 — Identification
ParameterValue
Product rangeTeSys
Product/component typeMotor starter
GV2ME06K2Q7 — Ratings
ParameterValue
Poles configuration3P
Breaking capacity50 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1
Utilisation categoryAC-3
GV2ME06K2Q7 — Mechanical
ParameterValue
Width45 mm
Height152 mm
Depth87 mm
GV2ME06K2Q7 — Other specifications
ParameterValue
Motor power0.37 kW at 400/415 V AC 50/60 Hz 0.55 kW at 400/415 V AC 50/60 Hz 0.37 kW at 440 V AC 50/60 Hz 0.55 kW at 440 V AC 50/60 Hz 0.37 kW at 500 V AC 50/60 Hz 0.55 kW at 500 V AC 50/60 Hz 0.75 kW at 500 V AC 50/60 Hz
Coordination typeType 1
Device short nameGV2ME
Device composition1 combination block GV2AF01 1 3-pole reversing contactor 1 motor circuit breaker type GV2ME
Motor starter typeReversing
Magnetic tripping current22.5 A
Coil voltage380/400 V AC 50/60 Hz
Thermal protection adjustment range1...1.6 A

Product details

The Schneider Electric GV2ME06K2Q7 is a DOL reversing combination motor starter from the TeSys GV2-ME range. It integrates a motor circuit breaker, a 3-pole reversing contactor, and a combination block (GV2AF01) into one pre-wired unit — a single order code that replaces three separate components on the BOM. Thermal protection adjusts from 1 to 1.6 A, so it's sized for small three-phase motors — think fractional-horsepower conveyors, fan coils, or pump drives. The magnetic trip is fixed at 22.5 A, which clears short-circuit faults fast without nuisance tripping on inrush. Rated for AC-3 utilisation category, meaning it's built for starting and stopping squirrel-cage induction motors under load — not just resistive switching. The 50 kA breaking capacity at 400/415 V AC (IEC 60947-4-1) means it safely interrupts fault currents up to that level without upstream fuses needing to clear first, as long as Type 1 coordination is acceptable.

The 45 mm wide footprint clips onto standard DIN rail. At 152 mm tall and 87 mm deep, it leaves room above for a control transformer or PLC output card. The reversing contactor is mechanically interlocked inside the assembly, so there's no risk of phase-to-phase short when the direction changes. Motor power output varies by supply voltage: 0.37 kW at 400 V, 0.55 kW at 440 V, and up to 0.75 kW at 500 V.

It is a current-production TeSys GV2-ME variant.

Frequently asked questions

What are the key ratings for the GV2ME06K2Q7?

Thermal protection range 1...1.6 A, magnetic trip fixed at 22.5 A, breaking capacity 50 kA at 400/415 V AC (IEC 60947-4-1), control voltage 380/400 V AC, and motor power up to 0.75 kW at 500 V AC.

What does the 50 kA breaking capacity mean for installation?

It means the starter can interrupt a short-circuit fault of up to 50 kA at 400 V without needing upstream fuses to clear first, as long as Type 1 coordination is acceptable — the starter may need replacement after a fault, but the downstream motor and wiring are protected.

MPN
GV2ME06K2Q7