Skip to main content
Schneider Electric GV2ME06K2U7 — Miniature Circuit Breakers (MCB)

Schneider Electric GV2ME06K2U7 TeSys reversing motor starter

MPNGV2ME06K2U7
Active

Schneider Electric TeSys GV2-ME reversing combination starter, GV2ME06K2U7, DOL, 1...1.6 A thermal adjustment, 230/240 V AC coil, 3-pole.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

GV2ME06K2U7 — Identification
ParameterValue
Product rangeTeSys
Product/component typeMotor starter
GV2ME06K2U7 — Ratings
ParameterValue
Poles configuration3P
Breaking capacity50 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1
Utilisation categoryAC-3
GV2ME06K2U7 — Mechanical
ParameterValue
Width45 mm
Height152 mm
Depth87 mm
GV2ME06K2U7 — Other specifications
ParameterValue
Motor power0.37 kW at 400/415 V AC 50/60 Hz 0.55 kW at 400/415 V AC 50/60 Hz 0.37 kW at 440 V AC 50/60 Hz 0.55 kW at 440 V AC 50/60 Hz 0.37 kW at 500 V AC 50/60 Hz 0.55 kW at 500 V AC 50/60 Hz 0.75 kW at 500 V AC 50/60 Hz
Coordination typeType 1
Device short nameGV2ME
Device composition1 motor circuit breaker type GV2ME 1 combination block GV2AF01 1 3-pole reversing contactor
Motor starter typeReversing
Magnetic tripping current22.5 A
Coil voltage230/240 V AC 50/60 Hz
Thermal protection adjustment range1...1.6 A

Product details

It is a 3-pole device rated for AC-3 utilisation category (motor switching), with a thermal protection adjustment range of 1 to 1.6 A.

The 45 mm width (three 18 mm modular pitches) and 87 mm depth leave room alongside other TeSys components for compact layouts. The 230/240 V AC control coil matches common panel control voltages across European and Asian installations. Motor power capability varies by line voltage: 0.37 kW at 400/415 V, 0.55 kW at 440 V, and up to 0.75 kW at 500 V — all at 50/60 Hz. The magnetic trip is fixed at 22.5 A.

Frequently asked questions

What is the thermal protection adjustment range?

The thermal overload relay adjusts from 1 A to 1.6 A. Set it to match the motor full-load current within that window.

What breaking capacity does this starter have?

It is rated for 50 kA at 400/415 V AC, 50 kA at 440 V AC, and 50 kA at 500 V AC, all conforming to IEC 60947-4-1.

What voltage does the control coil need?

The control circuit voltage is 230/240 V AC at 50/60 Hz.