Skip to main content
Schneider Electric GV2ME07A — Molded Case Circuit Breakers (MCCB)

Schneider GV2ME07A Motor Circuit Breaker, 2.5 A, Thermal-Mag

MPNGV2ME07A
Active

Schneider Electric TeSys GV2ME07A, 3-pole motor circuit breaker, 2.5 A rated current, thermal-magnetic trip, 100 kA breaking capacity at 400 V AC.

$109.65Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

GV2ME07A — Identification
ParameterValue
Product / component typeMotor circuit breaker
Device applicationMotor protection
GV2ME07A — Mechanical
ParameterValue
Height4.0 in (101 mm)
Width1.8 in (45 mm)
Depth3.09 in (78.5 mm)
GV2ME07A — Electrical
ParameterValue
Breaking capacity100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 100 kA Icu 440 V AC 50/60 Hz IEC 60947-2 100 kA Icu 500 V AC 50/60 Hz IEC 60947-2 3 kA Icu 690 V AC 50/60 Hz IEC 60947-2
[Ue] rated operational voltage690 V AC 50/60 Hz IEC 60947-2
[Ui] rated insulation voltage690 V AC 50/60 Hz IEC 60947-2
GV2ME07A — Specifications
ParameterValue
Poles description3P
Trip unit technologyThermal-magnetic
Device short nameGV2ME
StandardsEN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-2-40:Annex JJ IEC/EN 60335-1:Clause 30.2

Product details

The GV2ME07A is a three-pole motor circuit breaker from the TeSys GV2 family, set at a 2.5 A line rated current with a thermal-magnetic trip unit. It delivers a 100 kA breaking capacity (Icu) at 400 V AC per IEC 60947-2, making it suitable for high-fault-current panels while protecting motor circuits up to 0.75 kW at 400 V.

Ratings and fit for motor protection

The 2.5 A thermal setting matches motor full-load currents for 0.75 kW at 400/415 V or 1.1 kW at 500 V. The magnetic trip triggers at 39 A, providing short-circuit protection without nuisance tripping on starting. AC-3 utilization category confirms switching of squirrel-cage motors during starting and running. Phase failure sensitivity per IEC 60947-4-1 ensures the breaker trips on loss of one phase, preventing single-phase motor burnouts. Suitability for isolation (IEC 60947-1) means it can serve as a disconnecting means under load.

Current lifecycle stage. Compliant with UL 60947-4-1, CSA C22.2, and EN/IEC 60947-2.

Frequently asked questions

What are the key ratings of GV2ME07A?

It is a 2.5 A, 3-pole thermal-magnetic motor circuit breaker with 100 kA breaking capacity at 400 V AC, suitable for 0.75 kW motor loads at 400 V. It is rated for AC-3 duty and includes phase failure sensitivity.

What is the color of the GV2ME07A?

Dark grey.

What compliance documentation does this breaker carry?

It is certified to EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, and CSA C22.2 No 60947-4-1, covering motor protection and circuit breaker standards globally.

MPN
GV2ME07A