It is a 3-pole device with a rated current of 2.5 A, using a thermal-magnetic trip unit to provide overload and short-circuit protection for motors up to 0.75 kW at 400/415 V AC. The thermal element handles sustained overloads, while the magnetic trip is fixed at 39 A, clearing short-circuit faults. The breaker is rated for AC-3 and AC-3e utilisation categories, meaning it is suited for starting and stopping squirrel-cage motors under load, and it includes phase failure sensitivity per IEC 60947-4-1.
The power dissipation per pole is 2.5 W, which matters for thermal management inside a sealed enclosure. Mechanical durability is rated at 100,000 cycles, with electrical durability also at 100,000 cycles for AC-3 duty at 415 V. This gives a realistic service life for frequent motor starting applications like conveyors or pumps.
Dimensions are 89 mm high, 45 mm wide, and 78.5 mm deep, so it occupies a single 45 mm module width on the rail. It can be mounted horizontally or vertically. Power circuit connections use screw clamp terminals accepting 1 to 6 mm² solid or 1.5 to 6 mm² flexible wire, with a tightening torque of 1.7 N·m. The auxiliary contact block is integrated with 1 NO + 1 NC front-mounted contacts.
The GV2ME07AE11TQ is certified to EN/IEC 60947-2 (circuit-breakers) and EN/IEC 60947-4-1 (contactors and motor-starters), as well as UL 60947-4-1 and CSA C22.2 No 60947-4-1. It also complies with IEC/EN 60335-2-40 (Annex JJ) and IEC/EN 60335-1 (Clause 30.2) for heat and fire resistance, with a glow-wire test rating of 960 °C per IEC 60695-2-11.