Skip to main content
Schneider Electric GV2ME07K1B7 — Molded Case Circuit Breakers (MCCB)

Schneider TeSys GV2ME07K1B7 DOL Starter, 1.6-2.5 A, 24 V AC

MPNGV2ME07K1B7
Active

Schneider Electric TeSys GV2-ME DOL combination starter, GV2ME07K1B7, 1.6...2.5 A thermal adjustment, 24 V AC 50/60 Hz coil, 3-pole, non-reversing.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

GV2ME07K1B7 — Identification
ParameterValue
Product / component typeMotor starter
GV2ME07K1B7 — Mechanical
ParameterValue
Height152 mm
Width45 mm
Depth87 mm
GV2ME07K1B7 — Electrical
ParameterValue
Breaking capacity50 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1
GV2ME07K1B7 — Specifications
ParameterValue
Poles description3P
Device short nameGV2ME
GV2ME07K1B7 — Other specifications
ParameterValue
RangeTeSys
Motor power0.75 kW at 400/415 V AC 50/60 Hz 0.75 kW at 440 V AC 50/60 Hz 1.1 kW at 440 V AC 50/60 Hz 1.1 kW at 500 V AC 50/60 Hz
Coordination typeType 1
Device composition1 motor circuit breaker type GV2ME 1 3-pole contactor 1 combination block GV2AF01
Motor starter typeNon reversing
Utilisation categoryAC-3
Magnetic tripping current33.5 A
Coil voltage24 V AC 50/60 Hz
Thermal protection adjustment range1.6...2.5 A

Product details

The Schneider Electric TeSys GV2ME07K1B7 is a direct-on-line (DOL) combination motor starter — a single unit that integrates a 3-pole motor circuit breaker (GV2ME) and a 3-pole contactor, pre-assembled on a combination block (GV2AF01). It is a non-reversing starter, meaning it drives the motor in one direction only, which is the standard arrangement for pumps, fans, and conveyors that do not require reversing. The thermal protection adjustment range is 1.6 to 2.5 A, so it is sized for small three-phase motors — typically up to 0.75 kW at 400/415 V AC or 1.1 kW at 440/500 V AC under AC-3 duty (the standard utilisation category for squirrel-cage induction motors during starting and running).

It is part of the TeSys range, which means the combination block, auxiliary contacts, and busbar systems are shared across the GV2ME family. If you are standardising on TeSys for multiple motor sizes, the same wiring accessories and panel layout apply.

No broker or surplus channel needed. The combination block is factory-assembled, so the unit arrives as a single part number, not as loose components to be built up in the panel shop.

Frequently asked questions

What is the thermal protection adjustment range?

The thermal overload relay adjusts from 1.6 A to 2.5 A, covering small motors up to about 0.75 kW at 400 V or 1.1 kW at 440/500 V under AC-3 duty.

What control voltage does this starter use?

The coil is rated 24 V AC 50/60 Hz — a standard low-voltage control supply in industrial panels.

What is the breaking capacity?

50 kA at 400/415 V, 440 V, and 500 V, conforming to IEC 60947-4-1. This is a high-fault-rated unit suitable for installations with significant available fault current.

MPN
GV2ME07K1B7