The GV2ME07K1M7 is a non-reversing DOL combination starter from the TeSys GV2-ME series, integrating a 3-pole motor circuit breaker and a 3-pole contactor into one block with a GV2AF01 auxiliary contact block. It's designed for direct-on-line starting of three-phase induction motors up to 0.75 kW at 400/415 V AC (AC-3 duty). The thermal protection adjustment range is 1.6...2.5 A, and the magnetic trip is fixed at 33.5 A — so it protects the motor against overload and short-circuit in one package.
Rated breaking capacity is 50 kA Iq at 400/415 V AC, conforming to IEC 60947-4-1. That's enough to clear a high-fault bolted short without the upstream breaker needing to trip — as long as the coordination is Type 1, meaning the starter may need contact replacement after a fault, but the line stays coordinated.
Dimensions are 152 mm high, 45 mm wide, 87 mm deep — standard DIN-rail footprint for the TeSys GV2 series. The combination block clips onto the rail and the contactor and breaker are pre-wired internally, so panel wiring is just the incoming line, motor leads, and control coil connections.