The GV2ME07K2P7 is a TeSys GV2-ME DOL reversing combination starter — a single-block assembly that combines a motor circuit breaker (type GV2ME), a 3-pole reversing contactor, and the GV2AF01 combination block. It is sized for a 0.75 kW motor at 400/415 V AC (AC-3 duty) with a thermal protection adjustment range of 1.6...2.5 A and a 230 V AC control coil. The 50 kA breaking capacity at 400/415 V (conforming to IEC 60947-4-1) means it can safely interrupt a bolted fault up to that level without upstream damage, assuming Type 1 coordination.
The starter measures 45 mm wide by 152 mm high by 87 mm deep — a standard 45 mm modular width that clips onto a DIN rail. That depth (87 mm) is the dimension from the DIN-rail back to the front of the enclosure; account for it when sizing a shallow gland plate or a compact sub-panel.
The thermal protection adjustment range (1.6...2.5 A) sets the overload pickup — set it to the motor's full-load current, not the breaker's magnetic trip. The magnetic tripping current is fixed at 33.5 A, which clears short-circuit faults fast but does not protect against sustained overload (that is the thermal element's job). The 230 V AC control coil pulls from the control transformer; verify the coil rating matches your control voltage before wiring.