Skip to main content
Schneider Electric GV2ME07K2V7 — Miniature Circuit Breakers (MCB)

Schneider GV2ME07K2V7 TeSys reversing starter, 1.6-2.5 A, ob

MPNGV2ME07K2V7
Obsolete

Schneider TeSys GV2-ME reversing combination starter, GV2ME07K2V7, 1.6...2.5 A thermal protection, 400 V AC control, 3-pole, obsolete.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

GV2ME07K2V7 — Identification
ParameterValue
Product rangeTeSys
Product/component typeMotor starter
GV2ME07K2V7 — Ratings
ParameterValue
Poles configuration3P
Breaking capacity50 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1
Utilisation categoryAC-3
GV2ME07K2V7 — Mechanical
ParameterValue
Width45 mm
Height152 mm
Depth87 mm
GV2ME07K2V7 — Other specifications
ParameterValue
Motor power0.75 kW at 400/415 V AC 50/60 Hz 0.75 kW at 440 V AC 50/60 Hz 1.1 kW at 440 V AC 50/60 Hz 1.1 kW at 500 V AC 50/60 Hz
Coordination typeType 1
Device short nameGV2ME
Device composition1 combination block GV2AF01 1 3-pole reversing contactor 1 motor circuit breaker type GV2ME
Motor starter typeReversing
Magnetic tripping current33.5 A
Coil voltage400 V AC 50/60 Hz
Thermal protection adjustment range1.6...2.5 A

Product details

The Schneider TeSys GV2ME07K2V7 is a DOL reversing combination starter — a single assembly that bundles a motor circuit breaker (type GV2ME), a 3-pole reversing contactor, and a GV2AF01 combination block into one package. It is rated for AC-3 utilisation category (switching squirrel-cage motors), with a thermal protection adjustment range of 1.6...2.5 A and a magnetic trip threshold of 33.5 A. The 50 kA breaking capacity at 400/415 V AC (IEC 60947-4-1) means it can safely interrupt fault currents up to that level without upstream fuses needing to clear — a Type 1 coordination rating, so the starter may need contact replacement after a fault but the panel stays intact.

The unit measures 45 mm wide, 152 mm high, and 87 mm deep — a standard DIN-rail footprint that clips into a control panel enclosure. The 400 V AC control circuit voltage matches common European line voltages; the 3-pole design handles three-phase motor loads up to 0.75 kW at 400/415 V or 1.1 kW at 440/500 V. For a reversing application (e.g., conveyor direction change or actuator open/close), this single assembly replaces two separate contactors plus a thermal overload relay, saving panel space and wiring time.

Frequently asked questions

What are the key ratings for this reversing starter?

Thermal protection range 1.6...2.5 A, magnetic trip 33.5 A, breaking capacity 50 kA at 400/415 V AC (IEC 60947-4-1), motor power 0.75 kW at 400/415 V, AC-3 utilisation category.

What does the 50 kA breaking capacity mean for my panel?

It means the starter can interrupt fault currents up to 50 kA at 400/415 V without requiring upstream fuses to operate — the starter itself clears the fault. Type 1 coordination means the starter may need contact replacement after a fault, but the panel enclosure and buswork are protected.

What is the physical size of this starter?

Width 45 mm, height 152 mm, depth 87 mm — standard DIN-rail mount.

MPN
GV2ME07K2V7