Skip to main content
Schneider Electric GV2ME08K1FE7 — Miniature Circuit Breakers (MCB)

Schneider TeSys GV2ME08K1FE7 DOL Starter, 2.5-4 A, 115 V AC

MPNGV2ME08K1FE7
Active

Schneider Electric TeSys GV2-ME series, GV2ME08K1FE7, DOL combination starter, 2.5...4 A thermal protection, 115 V AC 50/60 Hz control voltage.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

GV2ME08K1FE7 — Identification
ParameterValue
Product rangeTeSys
Product/component typeMotor starter
GV2ME08K1FE7 — Ratings
ParameterValue
Poles configuration3P
Breaking capacity50 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1
Utilisation categoryAC-3
GV2ME08K1FE7 — Mechanical
ParameterValue
Width45 mm
Height152 mm
Depth87 mm
GV2ME08K1FE7 — Other specifications
ParameterValue
Motor power1.1 kW at 400/415 V AC 50/60 Hz 1.5 kW at 400/415 V AC 50/60 Hz 1.5 kW at 440 V AC 50/60 Hz 1.5 kW at 500 V AC 50/60 Hz 2.2 kW at 500 V AC 50/60 Hz
Coordination typeType 1
Device short nameGV2ME
Device composition1 motor circuit breaker type GV2ME 1 3-pole contactor 1 combination block GV2AF01
Motor starter typeNon reversing
Magnetic tripping current51 A
Coil voltage115 V AC 50/60 Hz
Thermal protection adjustment range2.5...4 A

Product details

The GV2ME08K1FE7 is a non-reversing DOL combination starter from the TeSys GV2-ME family, integrating a 3-pole motor circuit breaker and a contactor in one unit with a GV2AF01 combination block. It provides coordinated motor starting and protection in a single DIN-rail footprint. Thermal protection is adjustable from 2.5 to 4 A, covering small motor loads up to 1.1 kW at 400/415 V AC (AC-3 duty). The magnetic trip is fixed at 51 A, clearing short-circuit faults without nuisance tripping on motor inrush.

The TeSys GV2-ME series is a mature, widely stocked platform.

Panel integration

The combination block adds minimal depth beyond the breaker-contactor stack.

Frequently asked questions

What are the key ratings for this DOL starter?

Thermal protection range 2.5...4 A, magnetic trip at 51 A, control voltage 115 V AC 50/60 Hz, breaking capacity 50 kA at 400/415 V AC per IEC 60947-4-1, and motor power up to 1.1 kW at 400/415 V AC in AC-3 duty.

What coordination type does this starter use?

It is rated for Type 1 coordination per IEC 60947-4-1. After a short-circuit fault, the starter components may need replacement, but the upstream protection and bus remain undamaged.

MPN
GV2ME08K1FE7