The GV2ME08K1P7 is a non-reversing DOL combination starter from the TeSys Deca Frame 2 family. It integrates a GV2ME motor circuit breaker and a GV2AF01 combination block into a single 3-pole unit.
Rated breaking capacity is 50 kA Iq at 400/415 V, 440 V, and 500 V AC, conforming to IEC 60947-4-1. That 50 kA figure is the prospective fault current the device can safely interrupt — useful if your panel SCCR requirement is in that range. Coordination is Type 1, meaning after a fault the starter may need component replacement but the bus bars stay intact.
Motor power ratings across common voltages
Motor power depends on line voltage: 1.1 kW at 400/415 V, 1.5 kW at 440 V, and 2.2 kW at 500 V — all at 50/60 Hz. The 2.2 kW figure at 500 V is the highest rating in this adjustment range. If you're feeding a 400 V line, expect 1.1 kW maximum motor load.
Dimensions are 152 mm high, 45 mm wide, 87 mm deep. The combination block GV2AF01 is included, so the contactor and breaker are mechanically interlocked and pre-wired internally.