Skip to main content
Schneider Electric GV2ME08K1U7 — Miniature Circuit Breakers (MCB)

Schneider Electric GV2ME08K1U7 TeSys DOL Starter, 2.5-4 A, 2

MPNGV2ME08K1U7
Active

Schneider Electric TeSys GV2-ME DOL combination starter, GV2ME08K1U7, thermal protection 2.5...4 A, control circuit 230/240 V AC 50/60 Hz, 3-pole, non-reversing.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

GV2ME08K1U7 — Identification
ParameterValue
Product rangeTeSys
Product/component typeMotor starter
GV2ME08K1U7 — Ratings
ParameterValue
Poles configuration3P
Breaking capacity50 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1
Utilisation categoryAC-3
GV2ME08K1U7 — Mechanical
ParameterValue
Width45 mm
Height152 mm
Depth87 mm
GV2ME08K1U7 — Other specifications
ParameterValue
Motor power1.1 kW at 400/415 V AC 50/60 Hz 1.5 kW at 400/415 V AC 50/60 Hz 1.5 kW at 440 V AC 50/60 Hz 1.5 kW at 500 V AC 50/60 Hz 2.2 kW at 500 V AC 50/60 Hz
Coordination typeType 1
Device short nameGV2ME
Device composition1 motor circuit breaker type GV2ME 1 combination block GV2AF01 1 3-pole contactor
Motor starter typeNon reversing
Magnetic tripping current51 A
Coil voltage230/240 V AC 50/60 Hz
Thermal protection adjustment range2.5...4 A

Product details

The GV2ME08K1U7 is a TeSys GV2-ME direct-on-line combination starter from Schneider Electric — a motor circuit breaker, combination block, and 3-pole contactor in one assembly, non-reversing, with a 230/240 V AC 50/60 Hz control coil. Thermal protection adjusts from 2.5 to 4 A, and the magnetic trip is fixed at 51 A. The AC-3 utilisation category rating means it is sized for starting and stopping squirrel-cage motors under load — the 1.1 kW at 400/415 V AC is the real-world motor power it handles in that duty.

Coordination is Type 1, meaning after a fault the contactor may need replacement but the circuit breaker resets; acceptable for production lines where a quick swap is planned.

The combination block GV2AF01 is included in the assembly, so the contactor and breaker are mechanically interlocked and pre-wired; you land the incoming line and outgoing motor leads directly. Control voltage is 230/240 V AC, so the coil is compatible with common European and North American control transformers.

Frequently asked questions

What is the thermal protection adjustment range?

The thermal protection adjusts from 2.5 to 4 A, and the magnetic trip is fixed at 51 A.

What breaking capacity does it have?

It is rated 50 kA at 400/415 V AC conforming to IEC 60947-4-1, with the same 50 kA at 440 V and 500 V AC.

What control voltage does the coil require?

The control circuit voltage is 230/240 V AC 50/60 Hz.

MPN