Skip to main content
Schneider Electric GV2ME08K2M7 — Miniature Circuit Breakers (MCB)

Schneider Electric GV2ME08K2M7 TeSys reversing motor starter

MPNGV2ME08K2M7
Active

Schneider Electric TeSys GV2-ME reversing motor starter, GV2ME08K2M7, 2.5...4 A thermal protection, 220...230 V AC coil, 3-pole, 50 kA breaking capacity.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

GV2ME08K2M7 — Identification
ParameterValue
Product rangeTeSys
Product/component typeMotor starter
GV2ME08K2M7 — Ratings
ParameterValue
Poles configuration3P
Breaking capacity50 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1
Utilisation categoryAC-3
GV2ME08K2M7 — Mechanical
ParameterValue
Width45 mm
Height152 mm
Depth87 mm
GV2ME08K2M7 — Other specifications
ParameterValue
Motor power1.1 kW at 400/415 V AC 50/60 Hz 1.5 kW at 400/415 V AC 50/60 Hz 1.5 kW at 440 V AC 50/60 Hz 1.5 kW at 500 V AC 50/60 Hz 2.2 kW at 500 V AC 50/60 Hz
Coordination typeType 1
Device short nameGV2ME
Device composition1 motor circuit breaker type GV2ME 1 combination block GV2AF01 1 3-pole reversing contactor
Motor starter typeReversing
Magnetic tripping current51 A
Coil voltage220/230 V AC 50/60 Hz
Thermal protection adjustment range2.5...4 A

Product details

The Schneider Electric GV2ME08K2M7 is a TeSys GV2-ME reversing DOL combination starter, integrating a motor circuit breaker (GV2ME) with a reversing contactor block (GV2AF01) into a single 45 mm wide package. The thermal protection adjustment range is 2.5...4 A, which sets the overload trip point for the connected motor. The magnetic short-circuit trip is fixed at 51 A, providing instantaneous protection on high fault currents. Breaking capacity is 50 kA Iq at 400/415 V AC, conforming to IEC 60947-4-1 — this means the starter can safely interrupt a fault current up to 50 kA without welding its contacts or causing a cascade failure upstream, which is a strong SCCR for a compact motor starter.

Where you would use it

This is a panel-mounted reversing starter for a 1.1 kW motor at 400/415 V AC, or up to 2.2 kW at 500 V AC. The coordination type is Type 1, meaning under a short-circuit fault the starter may need contact replacement but the panel bus remains intact. For applications requiring no damage to the starter after a fault, you would need a Type 2 coordination study with upstream fuses or a specific circuit breaker.

Frequently asked questions

What are the key ratings for the GV2ME08K2M7?

Thermal protection range 2.5...4 A, magnetic trip at 51 A, breaking capacity 50 kA at 400/415 V AC, control voltage 220/230 V AC, and motor power up to 2.2 kW at 500 V AC.

What is the physical size of the GV2ME08K2M7?

Width 45 mm, height 152 mm, depth 87 mm. It mounts on a standard DIN rail.

What compliance documentation is available for the GV2ME08K2M7?

The part is rated to IEC 60947-4-1 for breaking capacity. Schneider Electric typically provides CE, UL, CSA, and CCC certifications for the TeSys GV2-ME series; confirm specific documentation with your order.

MPN
GV2ME08K2M7