Schneider Electric GV2ME08K2P7 — Miniature Circuit Breakers (MCB)

Schneider GV2ME08K2P7 TeSys reversing motor starter, 2.5-4 A

MPNGV2ME08K2P7
Obsolete

Schneider Electric TeSys GV2-ME reversing DOL combination starter, GV2ME08K2P7, 2.5...4 A thermal protection, 230 V AC control, 3-pole.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

GV2ME08K2P7 — Identification
ParameterValue
Product rangeTeSys
Product/component typeMotor starter
GV2ME08K2P7 — Ratings
ParameterValue
Poles configuration3P
Breaking capacity50 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1
Utilisation categoryAC-3
GV2ME08K2P7 — Mechanical
ParameterValue
Width45 mm
Height152 mm
Depth87 mm
GV2ME08K2P7 — Other specifications
ParameterValue
Motor power1.1 kW at 400/415 V AC 50/60 Hz 1.5 kW at 400/415 V AC 50/60 Hz 1.5 kW at 440 V AC 50/60 Hz 1.5 kW at 500 V AC 50/60 Hz 2.2 kW at 500 V AC 50/60 Hz
Coordination typeType 1
Device short nameGV2ME
Device composition1 motor circuit breaker type GV2ME 1 3-pole reversing contactor 1 combination block GV2AF01
Motor starter typeReversing
Magnetic tripping current51 A
Coil voltage230 V AC 50/60 Hz
Thermal protection adjustment range2.5...4 A

Product details

The GV2ME08K2P7 is a reversing direct-on-line (DOL) combination motor starter from the Schneider TeSys GV2-ME family. It integrates a 3-pole motor circuit breaker with thermal and magnetic protection, a reversing contactor pair, and an interlock block (GV2AF01) into a single 45 mm wide package that snaps onto DIN rail. Its thermal protection adjustment range of 2.5...4 A sets the overload trip point for the connected motor. The magnetic short-circuit trip is fixed at 51 A, providing instantaneous protection against high fault currents. Rated for AC-3 utilisation category (switching squirrel-cage motors), it delivers 50 kA breaking capacity at 400/415 V AC, certified to IEC 60947-4-1. Motor power ratings span 1.1 kW at 400/415 V up to 2.2 kW at 500 V, depending on line voltage.

The 2.5...4 A thermal adjustment range directly sets the full-load motor current you can protect. A motor nameplated at, say, 3.2 A FLA falls within this band; one at 5 A does not. The 51 A magnetic trip handles locked-rotor inrush without nuisance tripping on start. The 45 mm width and 152 mm height fit standard DIN-rail enclosures. Depth of 87 mm is the dimension from the DIN rail mounting surface to the front of the device — check gland-plate clearance if the enclosure is shallow.

Frequently asked questions

What is the thermal protection range of this starter?

The thermal overload adjustment range is 2.5 to 4 A. This sets the trip point for motor overload protection.

What breaking capacity does it offer?

It provides 50 kA breaking capacity at 400/415 V AC, 440 V AC, and 500 V AC, certified to IEC 60947-4-1.

What is the control voltage?

The control circuit voltage is 230 V AC at 50/60 Hz.

How do I source this obsolete part?

Since it is obsolete, sourcing is through surplus or broker channels. Submit an RFQ for a search of available inventory; no stock or lead-time can be stated upfront.

MPN
GV2ME08K2P7