Skip to main content
Schneider Electric GV2ME10AN11TQ — Molded Case Circuit Breakers (MCCB)

Schneider Electric GV2ME10AN11TQ Motor Circuit Breaker, 6.3

MPNGV2ME10AN11TQ
Obsolete

Schneider Electric TeSys GV2 motor circuit breaker, GV2ME10AN11TQ, 6.3 A rated current, 3-pole, thermal-magnetic trip, 100 kA breaking capacity at 400 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

GV2ME10AN11TQ — Identification
ParameterValue
Product / component typeMotor circuit breaker
Device applicationMotor protection
GV2ME10AN11TQ — Mechanical
ParameterValue
Height89 mm
Width54 mm
Depth78.5 mm
GV2ME10AN11TQ — Electrical
ParameterValue
[In] rated current6.3 A
Breaking capacity100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage600 V AC 50/60 Hz conforming to UL 508 690 V AC 50/60 Hz conforming to IEC 60947-2 600 V AC 50/60 Hz conforming to CSA C22.2 No 14
[Ui] rated insulation voltage690 V AC 50/60 Hz conforming to IEC 60947-2
GV2ME10AN11TQ — Specifications
ParameterValue
Poles description3P
Trip unit technologyThermal-magnetic
Device short nameGV2ME
StandardsEN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-2-40:Annex JJ IEC/EN 60335-1:Clause 30.2

Product details

Rated at 6.3 A continuous (In), it's sized for a 2.2 kW motor on a 400/415 V three-phase supply, or up to 4 kW at 690 V. Breaking capacity is 100 kA Icu at 400/415 V AC per IEC 60947-2, which means it can safely interrupt a fault current up to that level without welding contacts or cascading upstream — a strong SCCR figure for a 6 A frame.

IP20 finger-safe protection when open-mounted, so it's suitable for enclosed panels where the front face is behind a door. The dark grey housing carries an IK04 impact rating — tough enough for routine panel access. Wiring is via screw-clamp terminals accepting up to 6 mm² solid or 4 mm² flexible with ferrule. Torque to 1.7 N·m. The power circuit can take two conductors per terminal, handy for daisy-chaining to a contactor or overload relay.

Protection features and durability

Phase-failure sensitive per IEC 60947-4-1 — it will trip if one phase drops out, preventing single-phasing damage to the motor. Rated for uninterrupted duty (unlimited on-time) per IEC 60947-4-1. Electrical durability is 100,000 cycles at rated current in AC-3 (motor switching) duty; mechanical durability matches at 100,000 cycles. That's a solid service life for a panel-mounted motor starter.

Certified to EN/IEC 60947-2 (circuit-breaker standard) and EN/IEC 60947-4-1 (contactor/motor-starter standard), plus UL 60947-4-1 and CSA C22.2 No 60947-4-1 for North American installations. Also tested to IEC/EN 60335 for appliance applications (Annex JJ and Clause 30.2 glow-wire). Fire resistance tested to 960 °C per IEC 60695-2-11 (glow-wire). Climatic withstand conforms to IACS for marine environments. Operating altitude is limited to 2000 m without derating.

Frequently asked questions

What are the key ratings for the GV2ME10AN11TQ?

Rated current is 6.3 A (In). Breaking capacity is 100 kA Icu at 400/415 V AC, 50 kA at 500 V, and 3 kA at 690 V. Motor power ratings are 2.2 kW at 400/415 V, 3 kW at 500 V, and 4 kW at 690 V. Magnetic trip is fixed at 91 A.

What standards does the GV2ME10AN11TQ comply with?

It complies with EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, and IEC/EN 60335-2-40 Annex JJ and IEC/EN 60335-1 Clause 30.2 for glow-wire testing.

What is the physical size of the GV2ME10AN11TQ?

Dimensions are 89 mm high, 54 mm wide, and 78.5 mm deep. It mounts on a 35 mm DIN rail or to a panel with an adaptor plate.

Does the GV2ME10AN11TQ have phase failure protection?

Yes, it is phase-failure sensitive per IEC 60947-4-1, so it will trip if one phase is lost to prevent single-phasing motor damage.

MPN
GV2ME10AN11TQ