Skip to main content
Schneider Electric GV2ME10K1B7 — Miniature Circuit Breakers (MCB)

Schneider GV2ME10K1B7 TeSys DOL Starter, 4-6.3 A, 24 V AC

MPNGV2ME10K1B7
Active

Schneider Electric TeSys GV2-ME DOL combination motor starter, GV2ME10K1B7, thermal protection 4...6.3 A, 24 V AC 50/60 Hz control circuit.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

GV2ME10K1B7 — Identification
ParameterValue
Product rangeTeSys
Product/component typeMotor starter
GV2ME10K1B7 — Ratings
ParameterValue
Poles configuration3P
Breaking capacity50 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1
Utilisation categoryAC-3
GV2ME10K1B7 — Mechanical
ParameterValue
Width45 mm
Height152 mm
Depth87 mm
GV2ME10K1B7 — Other specifications
ParameterValue
Motor power2.2 kW at 400/415 V AC 50/60 Hz 2.2 kW at 440 V AC 50/60 Hz 3 kW at 440 V AC 50/60 Hz 3 kW at 500 V AC 50/60 Hz
Coordination typeType 1
Device short nameGV2ME
Device composition1 combination block GV2AF01 1 3-pole contactor 1 motor circuit breaker type GV2ME
Motor starter typeNon reversing
Magnetic tripping current78 A
Coil voltage24 V AC 50/60 Hz
Thermal protection adjustment range4...6.3 A

Product details

The GV2ME10K1B7 is a non-reversing DOL combination starter from the TeSys GV2-ME range, integrating a 3-pole motor circuit breaker and a 3-pole contactor in one block with the GV2AF01 base. The thermal protection adjustment range of 4...6.3 A sets the motor full-load current it protects — set the dial to match the nameplate FLA of the motor. The magnetic trip is fixed at 78 A, which clears short-circuit faults without nuisance tripping on inrush. Rated for AC-3 utilisation category, meaning it is designed for starting and stopping squirrel-cage induction motors under load. The motor power ratings span 2.2 kW at 400/415 V AC up to 3 kW at 500 V AC — match the voltage on your line to the kW column in the spec table. The 24 V AC control coil (50/60 Hz) is standard for PLC or relay-driven panels; verify your control transformer supplies 24 V AC, not DC. Breaking capacity is 50 kA Iq at 400/415 V, 440 V, and 500 V AC, conforming to IEC 60947-4-1. Coordination type is Type 1 per IEC 60947-4-1. Under a short-circuit, the contactor may need replacement after the fault, but the starter remains functional and the downstream motor is protected. If you need the contactor to survive a fault without replacement (Type 2 coordination), this is not the variant for that application.

The 45 mm width and 87 mm depth fit a typical motor control centre bucket or small enclosure. The 152 mm height is the tallest dimension — check clearance above the rail for wiring and the auxiliary contact block if fitted. The combination block GV2AF01 is included; no separate base ordering needed.

Frequently asked questions

What is the thermal protection adjustment range?

The thermal overload relay adjusts from 4 A to 6.3 A. Set the dial to match the motor nameplate full-load current within that window.

What control voltage does the coil require?

The control circuit voltage is 24 V AC at 50/60 Hz. Do not apply DC voltage to this coil variant.

What is the breaking capacity at 400 V?

50 kA Iq at 400/415 V AC, 50/60 Hz, conforming to IEC 60947-4-1. The same 50 kA rating applies at 440 V and 500 V AC.

What is the closest alternative in the same family?

Within the TeSys GV2-ME range, the key variant difference is the thermal adjustment range and coil voltage. For a different motor FLA, select the GV2ME part with the appropriate thermal range (e.g., GV2ME08 for 2.5-4 A, GV2ME14 for 6-10 A). For a different coil voltage, the suffix changes (e.g., GV2ME10K1 for 24 V AC, GV2ME10K2 for 48 V AC, GV2ME10K3 for 110 V AC). The physical footprint and breaking capacity are shared across the range.

MPN
GV2ME10K1B7