Skip to main content
Schneider Electric GV2ME10K1BW3 — Miniature Circuit Breakers (MCB)

Schneider TeSys GV2ME10K1BW3 Motor Starter, 4-6.3 A, 24 VDC

MPNGV2ME10K1BW3
Active

Schneider Electric TeSys Deca Frame 2, GV2ME10K1BW3, DOL combination starter, 4-6.3 A thermal range, 24 V DC coil.

$154.39Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

GV2ME10K1BW3 — Identification
ParameterValue
Product rangeTeSys
Product/component typeMotor starter
GV2ME10K1BW3 — Ratings
ParameterValue
Poles configuration3P
Breaking capacity50 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1
Utilisation categoryAC-3 AC-3e
GV2ME10K1BW3 — Mechanical
ParameterValue
Width45 mm
Height152 mm
Depth87 mm
GV2ME10K1BW3 — Other specifications
ParameterValue
Motor power2.2 kW at 400/415 V AC 50/60 Hz 2.2 kW at 440 V AC 50/60 Hz 3 kW at 440 V AC 50/60 Hz 3 kW at 500 V AC 50/60 Hz
Coordination typeType 1
Device short nameGV2ME
Device composition1 3-pole contactor 1 motor circuit breaker type GV2ME 1 combination block GV2AF01
Motor starter typeNon reversing
Magnetic tripping current78 A
Coil voltage24 V DC
Thermal protection adjustment range4...6.3 A

Product details

The GV2ME10K1BW3 is a direct-on-line (DOL) combination motor starter from the Schneider Electric TeSys range, built around a GV2ME10 motor circuit breaker and an LC1K06 contactor joined by a GV2AF01 combination block. It's a pre-assembled, non-reversing 3-pole starter rated for AC-3 and AC-3e utilisation categories — meaning it's designed for starting and stopping squirrel-cage motors under load, not just resistive switching. The thermal protection adjustment range spans 4 to 6.3 A, which covers small motor loads in the 2.2 kW to 3 kW band depending on line voltage. At 400/415 V AC it delivers 2.2 kW motor power; at 440 V it's rated for both 2.2 kW and 3 kW; at 500 V it handles 3 kW. The magnetic trip is fixed at 78 A, so instantaneous short-circuit protection kicks in well above the thermal setting — that's standard for motor starting inrush.

Breaking capacity is 50 kA Iq at 400/415 V, 440 V, and 500 V AC, conforming to IEC 60947-4-1. That 50 kA figure is the prospective fault current the starter can safely interrupt — important when the panel's available fault current is high. Coordination is Type 1, meaning after a short circuit the starter may need contactor or breaker replacement, but the installation is protected from fire or arc-flash. Control voltage is 24 V DC, which is common in PLC-driven panels and safety circuits. The coil on the LC1K06 contactor pulls in at 24 VDC nominal; verify your control transformer or power supply can deliver the inrush current for the contactor holding coil. The 24 VDC coil also simplifies integration with solid-state outputs from a safety relay or PLC. Physical footprint: 45 mm wide, 152 mm high, 87 mm deep. That 45 mm width is a single 9 mm DIN-module increment — it occupies two standard 22.5 mm module positions on the DIN rail. The depth of 87 mm means it clears most standard 100 mm-deep enclosures, but check gland-plate clearance if mounting near the back wall.

Frequently asked questions

What are the key ratings for this motor starter?

Thermal protection adjustment range is 4-6.3 A. Motor power is 2.2 kW at 400/415 V, up to 3 kW at 500 V. Breaking capacity is 50 kA at 400-500 V. Control voltage is 24 V DC. Magnetic trip is fixed at 78 A.

MPN
GV2ME10K1BW3