It integrates a motor circuit breaker (type GV2ME), a 3-pole contactor, and a combination block (GV2AF01) into a single non-reversing unit. The thermal protection adjustment range is 4...6.3 A, and the control circuit voltage is 220/230 V AC at 50/60 Hz. This is a 3-pole device rated for AC-3 utilization category, meaning it's designed for starting and stopping squirrel-cage induction motors under load.
The motor power ratings are 2.2 kW at 400/415 V AC and 3 kW at 500 V AC, both at 50/60 Hz. The breaking capacity is 50 kA at 400/415 V, 440 V, and 500 V AC conforming to IEC 60947-4-1.
Physical Integration
The device dimensions are 45 mm wide, 152 mm high, and 87 mm deep. This is a panel-mount unit, not a DIN-rail snap-on — it requires screw-mounting to a backplate or enclosure subpanel. The depth of 87 mm means you need at least that much clearance behind the panel door for wiring and the combination block.