Skip to main content
Schneider Electric GV2ME10K1P7 — Miniature Circuit Breakers (MCB)

TeSys GV2ME10K1P7 DOL Starter, 4...6.3 A, 50 kA Breaking

MPNGV2ME10K1P7
Obsolete

Schneider Electric TeSys GV2-ME DOL combination starter, GV2ME10K1P7, 4...6.3 A thermal adjustment, 230 V AC control, 50 kA breaking capacity.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

GV2ME10K1P7 — Identification
ParameterValue
Product rangeTeSys
Product/component typeMotor starter
GV2ME10K1P7 — Ratings
ParameterValue
Poles configuration3P
Breaking capacity50 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1
Utilisation categoryAC-3
GV2ME10K1P7 — Mechanical
ParameterValue
Width45 mm
Height152 mm
Depth87 mm
GV2ME10K1P7 — Other specifications
ParameterValue
Motor power2.2 kW at 400/415 V AC 50/60 Hz 2.2 kW at 440 V AC 50/60 Hz 3 kW at 440 V AC 50/60 Hz 3 kW at 500 V AC 50/60 Hz
Coordination typeType 1
Device short nameGV2ME
Device composition1 3-pole contactor 1 motor circuit breaker type GV2ME 1 combination block GV2AF01
Motor starter typeNon reversing
Magnetic tripping current78 A
Coil voltage230 V AC 50/60 Hz
Thermal protection adjustment range4...6.3 A

Product details

The GV2ME10K1P7 is a TeSys GV2-ME direct-on-line (DOL) combination starter from Schneider Electric. It integrates a 3-pole contactor, a GV2ME motor circuit breaker, and a GV2AF01 combination block into a single unit for non-reversing motor starting. The thermal protection adjustment range spans 4 to 6.3 A, and the magnetic tripping current is set at 78 A. This means the overload relay is sized for motors drawing between 4 and 6.3 A full-load current, while the magnetic short-circuit trip clears faults above 78 A instantaneously. The unit handles motor power up to 2.2 kW at 400/415 V AC and 3 kW at 500 V AC, making it suitable for small three-phase induction motors in pump, fan, or conveyor applications.

Breaking capacity is rated at 50 kA Iq at 400/415 V, 440 V, and 500 V AC, conforming to IEC 60947-4-1. Coordination type is Type 1, meaning the starter may need contactor replacement after a fault but the breaker resets.

If the application can accept a parametric substitute, the TeSys GV2ME series includes active variants with the same 4...6.3 A thermal range and 230 V AC coil, though the exact order code and physical footprint should be verified against the panel layout.

Physical integration

Dimensions are 152 mm height, 45 mm width, and 87 mm depth.

Frequently asked questions

What is the closest alternative to GV2ME10K1P7?

The TeSys GV2ME series includes active variants with the same 4...6.3 A thermal adjustment range and 230 V AC control voltage. Verify the exact order code and physical dimensions against your panel layout before substituting.

What is the breaking capacity of this starter?

The breaking capacity is 50 kA Iq at 400/415 V, 440 V, and 500 V AC, conforming to IEC 60947-4-1. This allows it to safely interrupt high fault currents.

What motor power range does this cover?

It handles motor power up to 2.2 kW at 400/415 V AC and 3 kW at 500 V AC, with a thermal adjustment range of 4 to 6.3 A.

MPN
GV2ME10K1P7