Skip to main content
Schneider Electric GV2ME10K1U7 — Miniature Circuit Breakers (MCB)

TeSys GV2ME10K1U7 DOL Motor Starter, 4-6.3 A, 230/240 V AC

MPNGV2ME10K1U7
Obsolete

Schneider Electric TeSys GV2-ME DOL combination starter, GV2ME10K1U7, 4...6.3 A thermal protection, 230...240 V AC control circuit.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

GV2ME10K1U7 — Identification
ParameterValue
Product rangeTeSys
Product/component typeMotor starter
GV2ME10K1U7 — Ratings
ParameterValue
Poles configuration3P
Breaking capacity50 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1
Utilisation categoryAC-3
GV2ME10K1U7 — Mechanical
ParameterValue
Width45 mm
Height152 mm
Depth87 mm
GV2ME10K1U7 — Other specifications
ParameterValue
Motor power2.2 kW at 400/415 V AC 50/60 Hz 2.2 kW at 440 V AC 50/60 Hz 3 kW at 440 V AC 50/60 Hz 3 kW at 500 V AC 50/60 Hz
Coordination typeType 1
Device short nameGV2ME
Device composition1 combination block GV2AF01 1 3-pole contactor 1 motor circuit breaker type GV2ME
Motor starter typeNon reversing
Magnetic tripping current78 A
Coil voltage230/240 V AC 50/60 Hz
Thermal protection adjustment range4...6.3 A

Product details

The GV2ME10K1U7 is a TeSys GV2-ME direct-on-line (DOL) motor starter from Schneider Electric, combining a 3-pole contactor and a motor circuit breaker in one block. It's rated for AC-3 duty with a thermal protection adjustment range of 4 to 6.3 A and a control circuit voltage of 230/240 V AC at 50/60 Hz. The magnetic tripping current is set at 78 A, and the unit delivers a breaking capacity of 50 kA Iq at 400/415 V AC, conforming to IEC 60947-4-1.

The 4 to 6.3 A thermal adjustment range covers small motor loads — think fractional-horsepower pumps, small conveyors, or fan drives up to 2.2 kW at 400/415 V or 3 kW at 500 V. The 230/240 V AC control coil is standard for European and many Asian control panels. The 78 A magnetic trip point provides instantaneous short-circuit protection, while the thermal bimetallic element handles overloads — a classic combination that's been reliable in the field for decades.

Integration Notes

The unit measures 152 mm high by 45 mm wide by 87 mm deep, fitting a standard DIN-rail footprint. The combination block includes a GV2AF01 auxiliary contact block as standard. It's a non-reversing starter, so for reversing applications you'd need two units or a separate reversing contactor.

Frequently asked questions

What are the key ratings for this motor starter?

Thermal protection range 4 to 6.3 A, control voltage 230/240 V AC, magnetic trip at 78 A, breaking capacity 50 kA at 400/415 V AC, and motor power up to 2.2 kW at 400/415 V or 3 kW at 500 V.

What is the physical size of the GV2ME10K1U7?

It measures 152 mm high, 45 mm wide, and 87 mm deep, fitting a standard DIN-rail mount.

How do I source this obsolete part?

It's sourced to order against an RFQ through surplus inventory channels. No factory stock remains.

MPN
GV2ME10K1U7