Schneider GV2ME10K2B7 TeSys reversing starter, 4-6.3A, 24V A

MPNGV2ME10K2B7
Obsolete

Schneider Electric TeSys GV2-ME reversing DOL combination starter, GV2ME10K2B7, thermal adjustment 4...6.3 A, 24 V AC control coil.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

GV2ME10K2B7 — Identification
ParameterValue
Product rangeTeSys
Product/component typeMotor starter

Ratings

GV2ME10K2B7 — Ratings
ParameterValue
Poles configuration3P
Breaking capacity50 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1
Utilisation categoryAC-3

Mechanical

GV2ME10K2B7 — Mechanical
ParameterValue
Width45 mm
Height152 mm
Depth87 mm

Other specifications

GV2ME10K2B7 — Other specifications
ParameterValue
Motor power2.2 kW at 400/415 V AC 50/60 Hz 2.2 kW at 440 V AC 50/60 Hz 3 kW at 440 V AC 50/60 Hz 3 kW at 500 V AC 50/60 Hz
Coordination typeType 1
Device short nameGV2ME
Device composition1 motor circuit breaker type GV2ME 1 combination block GV2AF01 1 3-pole reversing contactor
Motor starter typeReversing
Magnetic tripping current78 A
Coil voltage24 V AC 50/60 Hz
Thermal protection adjustment range4...6.3 A

Product details

The GV2ME10K2B7 is a TeSys GV2-ME reversing DOL combination starter — a single-package unit integrating a 3-pole motor circuit breaker (type GV2ME), a combination block (GV2AF01), and a 3-pole reversing contactor, all pre-wired for reversing duty. Thermal protection adjusts from 4 to 6.3 A, and the control circuit runs on 24 V AC 50/60 Hz. Rated for AC-3 utilisation category, it delivers 50 kA breaking capacity (Iq) at 400/415 V and 440 V, and 50 kA at 500 V, all conforming to IEC 60947-4-1. Coordination type is Type 1.

The 4...6.3 A thermal adjustment range sets the motor full-load current window. For a 2.2 kW motor at 400/415 V or a 3 kW motor at 440/500 V, this starter is sized correctly — the magnetic trip threshold is 78 A, which clears a locked-rotor event without nuisance tripping on normal starting inrush. The Type 1 coordination allows the contactor to be damaged during a fault and require replacement, but the breaker clears the fault. The reversing contactor pair is built in, so no external reversing contactor or mechanical interlock is needed. The 24 V AC control coil matches standard control transformer outputs in many panels.

Mounts on DIN rail. The 3-pole design handles three-phase motor circuits.

Frequently asked questions

What replaces the GV2ME10K2B7?

There is no officially listed successor order code for this obsolete part. For a like-for-like fit, you would need to evaluate current TeSys GV2 or GV3 series starters with the same thermal range and reversing capability; consult with engineering for a drop-in or panel-mod alternative.

What are the key ratings I need to verify for fit?

Thermal adjustment 4...6.3 A, magnetic trip at 78 A, AC-3 utilisation category, 50 kA breaking capacity at 400/415 V, and 24 V AC control voltage. Motor power is 2.2 kW at 400/415 V and 3 kW at 440/500 V.

How do I source this part since it's obsolete?

Send an RFQ. We can check surplus and broker inventory against your requirement. No stock count or lead time can be guaranteed without a live quote.

MPN