Rated for AC-3 duty (motor switching), it covers motor loads up to 3 kW at 500 V AC and 2.2 kW at 400/415 V AC, with a thermal protection adjustment range of 4 to 6.3 A. The magnetic trip is fixed at 78 A, providing short-circuit protection that coordinates with the thermal overload for Type 1 coordination — meaning the starter may need component replacement after a fault, but the downstream equipment stays protected.
Breaking capacity is 50 kA Iq at 400/415 V AC, 440 V AC, and 500 V AC, all conforming to IEC 60947-4-1 — that standard covers the combination starter as a whole, not just the breaker section, so the assembly is rated to clear a bolted fault up to 50 kA without catastrophic failure.
Panel footprint is 45 mm wide by 152 mm tall by 87 mm deep — standard for the TeSys GV2-ME range, clips onto 35 mm DIN rail.