Skip to main content
Schneider Electric GV2ME10K2F7 — Molded Case Circuit Breakers (MCCB)

Schneider GV2ME10K2F7 TeSys Reversing Starter, 4-6.3 A, Obso

MPNGV2ME10K2F7
Active

Schneider Electric TeSys GV2-ME reversing DOL combination starter, GV2ME10K2F7, 4…6.3 A thermal adjustment, 110 V AC coil, 3-pole, obsolete.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

GV2ME10K2F7 — Identification
ParameterValue
Product / component typeMotor starter
GV2ME10K2F7 — Mechanical
ParameterValue
Height152 mm
Width45 mm
Depth87 mm
GV2ME10K2F7 — Electrical
ParameterValue
Breaking capacity50 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1
GV2ME10K2F7 — Specifications
ParameterValue
Poles description3P
Device short nameGV2ME
GV2ME10K2F7 — Other specifications
ParameterValue
RangeTeSys
Motor power2.2 kW at 400/415 V AC 50/60 Hz 2.2 kW at 440 V AC 50/60 Hz 3 kW at 440 V AC 50/60 Hz 3 kW at 500 V AC 50/60 Hz
Coordination typeType 1
Device composition1 combination block GV2AF01 1 motor circuit breaker type GV2ME 1 3-pole reversing contactor
Motor starter typeReversing
Utilisation categoryAC-3
Magnetic tripping current78 A
Coil voltage110 V AC 50/60 Hz
Thermal protection adjustment range4...6.3 A

Product details

Rated for AC-3 duty (motor switching), it covers motor loads up to 3 kW at 500 V AC and 2.2 kW at 400/415 V AC, with a thermal protection adjustment range of 4 to 6.3 A. The magnetic trip is fixed at 78 A, providing short-circuit protection that coordinates with the thermal overload for Type 1 coordination — meaning the starter may need component replacement after a fault, but the downstream equipment stays protected.

Breaking capacity is 50 kA Iq at 400/415 V AC, 440 V AC, and 500 V AC, all conforming to IEC 60947-4-1 — that standard covers the combination starter as a whole, not just the breaker section, so the assembly is rated to clear a bolted fault up to 50 kA without catastrophic failure.

Panel footprint is 45 mm wide by 152 mm tall by 87 mm deep — standard for the TeSys GV2-ME range, clips onto 35 mm DIN rail.

Frequently asked questions

What is the thermal protection adjustment range?

4 to 6.3 A, set via the dial on the front of the motor circuit breaker section.

What breaking capacity does it have?

50 kA Iq at 400/415 V, 440 V, and 500 V AC, per IEC 60947-4-1.

What control voltage does the coil need?

110 V AC at 50/60 Hz.

How do I source this obsolete part?

Submit an RFQ with your quantity and target delivery. We source through our broker network for new-old-stock and verified surplus — no lead-time promise without a quote, but the network is deep on TeSys GV2-ME parts.

MPN
GV2ME10K2F7