The thermal protection adjustment range is 4...6.3 A, and the control circuit is 230 V AC 50/60 Hz. Rated for AC-3 utilisation category, this starter handles reversing motor duty directly — no external interlocking required. Motor power ratings reach 2.2 kW at 400/415 V AC and 3 kW at 440/500 V AC (50/60 Hz). The magnetic trip is set at 78 A, providing short-circuit protection coordinated to Type 1. Breaking capacity is 50 kA Iq at 400/415 V, 440 V, and 500 V AC, conforming to IEC 60947-4-1.
This is a DIN-rail mounted combination starter — the breaker and contactor arrive pre-assembled with the GV2AF01 interconnection block, so panel wiring reduces to the power feed and motor leads. Dimensions are 45 mm wide, 152 mm high, and 87 mm deep, fitting standard enclosure layouts.