Skip to main content
Schneider Electric GV2ME10K2P7 — Miniature Circuit Breakers (MCB)

Schneider GV2ME10K2P7 TeSys DOL Reversing Starter, 4-6.3 A,

MPNGV2ME10K2P7
Active

Schneider Electric TeSys GV2-ME DOL reversing combination motor starter, GV2ME10K2P7, thermal protection 4...6.3 A, 230 V AC control voltage.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

GV2ME10K2P7 — Identification
ParameterValue
Product rangeTeSys
Product/component typeMotor starter

Ratings

GV2ME10K2P7 — Ratings
ParameterValue
Poles configuration3P
Breaking capacity50 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1
Utilisation categoryAC-3

Mechanical

GV2ME10K2P7 — Mechanical
ParameterValue
Width45 mm
Height152 mm
Depth87 mm

Other specifications

GV2ME10K2P7 — Other specifications
ParameterValue
Motor power2.2 kW at 400/415 V AC 50/60 Hz 2.2 kW at 440 V AC 50/60 Hz 3 kW at 440 V AC 50/60 Hz 3 kW at 500 V AC 50/60 Hz
Coordination typeType 1
Device short nameGV2ME
Device composition1 combination block GV2AF01 1 motor circuit breaker type GV2ME 1 3-pole reversing contactor
Motor starter typeReversing
Magnetic tripping current78 A
Coil voltage230 V AC 50/60 Hz
Thermal protection adjustment range4...6.3 A

Product details

The thermal protection adjustment range is 4...6.3 A, and the control circuit is 230 V AC 50/60 Hz. Rated for AC-3 utilisation category, this starter handles reversing motor duty directly — no external interlocking required. Motor power ratings reach 2.2 kW at 400/415 V AC and 3 kW at 440/500 V AC (50/60 Hz). The magnetic trip is set at 78 A, providing short-circuit protection coordinated to Type 1. Breaking capacity is 50 kA Iq at 400/415 V, 440 V, and 500 V AC, conforming to IEC 60947-4-1.

This is a DIN-rail mounted combination starter — the breaker and contactor arrive pre-assembled with the GV2AF01 interconnection block, so panel wiring reduces to the power feed and motor leads. Dimensions are 45 mm wide, 152 mm high, and 87 mm deep, fitting standard enclosure layouts.

Frequently asked questions

What is the thermal protection adjustment range?

The thermal overload adjustment range is 4...6.3 A, set via the dial on the motor circuit breaker section of the combination starter.

What motor power can this starter handle?

At 400/415 V AC it handles 2.2 kW; at 440 V AC it handles 2.2 kW; at 500 V AC it handles 3 kW. All ratings are for 50/60 Hz three-phase induction motors in AC-3 duty.

What is the breaking capacity?

50 kA Iq at 400/415 V, 440 V, and 500 V AC, conforming to IEC 60947-4-1. This is the short-circuit current the starter can safely interrupt at those voltages.

What control voltage does the coil require?

230 V AC at 50/60 Hz. This is the voltage applied to the reversing contactor coil.

MPN
GV2ME10K2P7