Schneider Electric GV2ME10K2Q7 — Miniature Circuit Breakers (MCB)

Schneider Electric GV2ME10K2Q7 TeSys DOL Reversing Starter,

MPNGV2ME10K2Q7
Obsolete

Schneider Electric TeSys GV2-ME series, DOL reversing combination starter, GV2ME10K2Q7, thermal protection 4...6.3 A, 380...400 V AC control circuit, 50 kA breaking capacity at 400 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

GV2ME10K2Q7 — Identification
ParameterValue
Product rangeTeSys
Product/component typeMotor starter

Ratings

GV2ME10K2Q7 — Ratings
ParameterValue
Poles configuration3P
Breaking capacity50 kA Iq at 400/415 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 440 V AC 50/60 Hz conforming to IEC 60947-4-1 50 kA Iq at 500 V AC 50/60 Hz conforming to IEC 60947-4-1
Utilisation categoryAC-3

Mechanical

GV2ME10K2Q7 — Mechanical
ParameterValue
Width45 mm
Height152 mm
Depth87 mm

Other specifications

GV2ME10K2Q7 — Other specifications
ParameterValue
Motor power2.2 kW at 400/415 V AC 50/60 Hz 2.2 kW at 440 V AC 50/60 Hz 3 kW at 440 V AC 50/60 Hz 3 kW at 500 V AC 50/60 Hz
Coordination typeType 1
Device short nameGV2ME
Device composition1 combination block GV2AF01 1 motor circuit breaker type GV2ME 1 3-pole reversing contactor
Motor starter typeReversing
Magnetic tripping current78 A
Coil voltage380/400 V AC 50/60 Hz
Thermal protection adjustment range4...6.3 A

Product details

The GV2ME10K2Q7 is a DOL reversing combination starter from the TeSys GV2-ME series, built as a motor circuit breaker paired with a 3-pole reversing contactor in one block. It provides thermal protection adjustable from 4 to 6.3 A and magnetic tripping at 78 A, rated for AC-3 duty (motor switching) up to 3 kW at 500 V AC. Coordination is Type 1, so after a fault the starter may need replacement, but the upstream gear stays untouched. Control circuit voltage is 380/400 V AC, so it's wired directly from the motor supply on a 400 V line — no separate control transformer needed for the coil.

The starter measures 45 mm wide, 152 mm high, and 87 mm deep — a standard TeSys GV2 footprint that clips onto a DIN rail. The reversing contactor and breaker are factory-assembled, so it lands as one unit ready to wire. No need to gut the whole line to swap it in; it meets the old footprint.

Frequently asked questions

What is the breaking capacity and what does it mean for my panel?

The GV2ME10K2Q7 is rated for 50 kA breaking capacity at 400/415 V AC (IEC 60947-4-1). That means it can safely interrupt a fault current up to 50 kA without the upstream breaker needing to trip — a strong selectivity advantage in high-fault-capacity installations.

What motor power can this starter handle?

It covers motor loads up to 3 kW at 500 V AC, 2.2 kW at 400/415 V AC, and 2.2 kW at 440 V AC — all at 50/60 Hz. The thermal adjustment range of 4 to 6.3 A sets the actual motor FLC it protects.

MPN
GV2ME10K2Q7